beautypg.com

Using the generator, System ground, Connecting to a building’s electrical system – Briggs & Stratton PowerBoss 30211 User Manual

Page 9: Generator location, Warning

background image

9

5500W Portable Generator

USING THE GENERATOR

System Ground

The generator has a system ground that connects the
generator frame components to the ground terminals on
the AC output receptacles.The system ground is connected
to the AC neutral wire (the neutral is bonded to the
generator frame).

Special Requirements

There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes, or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction.

• In some areas, generators are required to be registered

with local utility companies.

• If the generator is used at a construction site, there may

be additional regulations which must be observed.

Connecting to a Building’s Electrical

System

Connections for standby power to a building’s electrical
system must be made by a qualified electrician.The
connection must isolate the generator power from utility
power, and must comply with all applicable laws and
electrical codes.

Generator Location

Generator Clearance

The generator must be at least 5 ft. (152 cm) from
structures having combustible walls and/or other
combustible materials. Leave at least 3 ft. (92 cm) all around
generator including overhead, for adequate cooling,
maintenance and servicing.

Place generator in a well ventilated area, which will allow
for removal of deadly exhaust gas. DO NOT place
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area (Figure 4). Prevailing winds
and air currents should be taken into consideration when
positioning generator.

• When using generator for backup power, notify utility

company. Use approved transfer equipment to isolate
generator from electric utility.

• Use a ground fault circuit interrupter (GFCI) in any damp or

highly conductive area, such as metal decking or steel work.

• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn,

frayed, bare or otherwise damaged.

• DO NOT operate generator in the rain.
• DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

• DO NOT allow unqualified persons or children to operate or

service generator.

Generator produces powerful voltage.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.

WARNING

Figure 4 — Generator Clearance

Exhaust Port

Typical Generator Shown

• Operate generator ONLY outdoors.
• Keep exhaust gas from entering a confined area through

windows, doors, ventilation intakes or other openings.

• DO NOT operate generator inside any building or enclosure,

including the generator compartment of a recreational vehicle (RV).

Running generator gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide will cause nausea,
fainting or death.

WARNING