Specifications – Bryant Electric Air Conditoner 597C User Manual
Page 4
—4—
SPECIFICATIONS
See notes on page 5.
UNIT SIZE-SERIES
018-F
024-F
030-F
036-F
042-F
048-G/F
060-F
Operating Weight (Lb)
149
187
197
197
207
261
265
ELECTRICAL
Unit Volts—Hertz—Phase
208/230—60—1
208/230—60—1
208/230—60—1
208/230—60—1
208/230—60—1
208/230—1—60
208/230—1—60
Operating Voltage Range
*
187—253
187—253
187—253
187—253
187—253
187—253
187—253
Compressor— Rated Load Amps
10.0
11.4
15.0
17.9
20.0
23.7/19.9
28.8
Locked Rotor Amps
41.0
56.0
72.5
88.0
104.0
129.0/137.0
169.0
Condenser Fan Motor—Full Load Amps
0.5
0.5
0.5
1.1
1.1
1.1
1.4
Min Unit Ampacity for Wire Sizing
13.0
14.8
19.3
23.4
26.0
30.5/26.0
37.4
Min Wire Size (60°C Copper) AWG†
14
14
14
12
10
8/10
8
Min Wire Size (75°C Copper) AWG†
14
14
14
12
10
10
8
Max Wire Length (60°C) (Ft)‡
61
53
39
52
77
77
82
Max Wire Length (75°C) (Ft)‡
58
50
37
50
73
61
78
Max Branch Circuit Fuse Size (Amps)
**
20
20
30
40
40
50/40
60
COMPRESSOR & REFRIGERANT
Compressor— Manufacturer
Copeland
Type
Scroll
Temperature & Current Protection
Internal Line Break
Refrigerant— Type
R-22
Amount @ 15 Ft ††
4.25
5.25
6.25
6.25
7.00
10.50
11.00
CONDENSER COIL & FAN
Coil Face Area (Sq Ft)
10.9
12.2
15.2
15.2
18.3
18.3
18.3
Fins Per In.—Rows—Circuits
25—1—2
25—1—2
25—1—3
25—1—3
25—1—4
20—2—5
20—2—6
Fan Motor—PSC Type, HP & RPM
1/15 & 800
1/5 & 825
1/4 & 1125
Volts—Hertz—Phase
208/230—60—1
Condenser Airflow (CFM)
1500
2000
2000
3000
3000
3000
3300
OPTIONAL EQUIPMENT
Support Feet
KSASF0101AAA
Coastal Filter
KAACF0101SML
KAACF0201MED
Time Delay Relay
KAATD0101TDR
Cycle Protector
KSACY0101AAA
Crankcase Heater
KAACH1201AAA
Start Assist—Capacitor/Relay Type
KSAHS1501AAA
KSAHS1601AAA
Start Assist—PTC Type
KAACS0201PTC
TXV (RPB)
KAATX0201RPB
KAATX0301RPB
KAATX0401RPB
KAATX0501RPB
KAATX0601RPB
KAATX0701RPB
TXV (Hard Shutoff)‡‡
KSATX0601HSO
KSATX0701HSO
Low-Pressure Switch
KAALP0101LPS
High-Pressure Switch
KSAHI0101HPS
Filter Drier
P502-8083S (RCD)
P502-8163S (RCD)
Evaporator Freeze Thermostat
***
KAAFT0101AAA
Liquid-Line Solenoid Valve
KAALS0101LLS
Winter Start Control
***
KAAWS0101AAA
Low-Ambient Pressure Switch
KSALA0201R22
Low-Ambient Controller
P251-0083 (RCD)
MotorMaster® Control†††
32LT660004 (RCD)
Ball Bearing Fan Motor
Not Available
HC38GE231 (RCD)
HC40GE232
(RCD)
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBPAC01-B
Thermidistat™ Control—
Programmable/ Non-Programmable Thermostat
with Humidity Control
TSTATBBPRH01-B
Builder’s Thermostat, Manual Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBBAC01-B
Outdoor Air Temperature Sensor
TSTATXXSEN01-B
Backplate for Builder’s Thermostat
TSTATXXBBP01
Backplate for Non-Programmable Thermostat
TSTATXXNBP01
Backplate for Programmable Thermostat
TSTATXXPBP01
Thermostat Conversion Kit (4 to 5 wire)
TSTATXXCNV10