beautypg.com

Caution, Masonry insert installation – New Buck Corporation 18 User Manual

Page 7

background image

SECTION II

MASONRY

INSERT

INSTALLATION

The Model 18 may be installed using an all masonry fireplace built in accordance with the
Uniform Building Code and National Fire Protection Association (NFPA). The first step in
this type of installation is to determine the acceptability of the fireplace and chimney for use
with a woodstove. Both the construction and condition of the fireplace are important consid-
erations when installing a woodstove. NOTE: It is not necessary to direct connect this
unit unless installed in improper drawing fireplace or oversized flue. The chimney
should extend at least 3' above the roof and at least 2' above any point of the roof
within 10'.

CAUTION


REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE
BEFORE YOU INSTALL YOUR STOVE.


MINIMUM CLEARANCES



A. Unit to adjust to Side Wall
B. Front Floor Protector
C. Side Floor Protector
D. Side Wood Trim
E. Top Wood Trim
F. Mantel or Brackets

MODEL 18
10"
16"
8"
9"
14"
21"

F

B

A

E

C

D

FIGURE 1

5