Bryant 583B User Manual

Page 9

background image

—9—

BASE UNIT DIMENSIONS — 583B024-036

REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall

system, then the system performance may be compromised.

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)

NEC REQ’D CLEARANCES. in. (mm)

Between units, power entry side

. . . . . . . . . . . . . . 42 (1066.8)

Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . . 42 (1066.8)

LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. [MM]

“A”

CENTER OF GRAVITY

IN. [MM]

lb.

kg.

X

Y

Z

583B042060/090

208/230-1-60
208/230-3-60

460-3-60

382

173.3

38.98 [990.2]

23.0 [584.2]

16.3 [412.8]

16.6 [421.6]

583B048090/115/130

208/230-1-60
208/230-3-60

460-3-60

421

191.0

38.98 [990.2]

21.5 [546.1]

16.6 [422.1]

18.0 [457.2]

583B060090/115/130

208/230-1-60,
208/230-3-60,

460-3-60

468

212.3

42.98 [1091.7]

23.5 [596.9]

16.3 [412.8]

17.6 [447.0]