FAN PERFORMANCE (cont.)
Table 41 – 580J*06
1 PHASE
5 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1500
800
0.39
904
0.49
999
0.60
1087
0.72
1169
0.85
1625
849
0.48
947
0.59
1038
0.70
1122
0.83
1201
0.96
1750
899
0.59
992
0.70
1078
0.82
1159
0.95
1235
1.08
1875
950
0.70
1038
0.82
1120
0.95
1198
1.08
1271
1.22
2000
1001
0.84
1085
0.96
1163
1.09
1238
1.23
1309
1.38
2125
1053
0.99
1133
1.12
1208
1.26
1280
1.40
---
---
2250
1106
1.16
1182
1.29
1254
1.44
---
---
---
---
2375
1159
1.34
1231
1.49
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1247
0.98
1320
1.13
1390
1.28
1457
1.44
---
---
1625
1276
1.10
1348
1.24
1416
1.40
---
---
---
---
1750
1308
1.22
1377
1.38
---
---
---
---
---
---
1875
1342
1.37
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
2125
---
---
---
---
---
---
---
---
---
---
2250
---
---
---
---
---
---
---
---
---
---
2375
---
---
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes.
Table 42 – 580J*06
1 PHASE
5 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1500
848
0.42
968
0.55
1069
0.68
1158
0.80
1238
0.94
1625
897
0.51
1013
0.65
1111
0.79
1198
0.93
1277
1.07
1750
947
0.61
1059
0.76
1155
0.91
1240
1.06
1318
1.21
1875
997
0.72
1105
0.89
1199
1.05
1283
1.21
1359
1.37
2000
1048
0.85
1153
1.03
1244
1.20
1326
1.37
---
---
2125
1100
1.00
1201
1.19
1290
1.37
---
---
---
---
2250
1152
1.16
1250
1.36
---
---
---
---
---
---
2375
1205
1.34
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field---Supplied Drive
1
1500
1312
1.07
1380
1.20
1445
1.34
1506
1.48
---
---
1625
1350
1.21
1418
1.35
1482
1.50
---
---
---
---
1750
1390
1.36
---
---
---
---
---
---
---
---
1875
---
---
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
2125
---
---
---
---
---
---
---
---
---
---
2250
---
---
---
---
---
---
---
---
---
---
2375
---
---
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes.
Boldface indicates field supplied drive is required.
1. Recommend using field supplied motor pulley (part no. KR11HY171) and belt (part no. KR30AE039).
580J