Curbs & weights dimensions j*04 (cont.) – Bryant LEGACY LINE 580J User Manual
Page 18

18
CURBS & WEIGHTS DIMENSIONS -- 580J*04--07 (cont.)
C08599
Fig. 2 -- Dimensions 580J 04--07
C
B
A
D
C08337
Fig. 3 -- Service Clearance
LOC
DIMENSION
CONDITION
A
48---in (1219 mm)
Unit disconnect is mounted on panel
18---in (457 mm)
No disconnect, convenience outlet option
18---in (457 mm)
Recommended service clearance
12---in (305 mm)
Minimum clearance
B
42---in (1067 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall)
36---in (914 mm)
Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special
Check for sources of flue products within 10---ft of unit fresh air intake hood
C
36---in (914 mm)
Side condensate drain is used
18---in (457 mm)
Minimum clearance
D
48---in (1219 mm)
No flue discharge accessory installed, surface is combustible material
42---in (1067 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36---in (914 mm)
Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass)
Special
Check for adjacent units or building fresh air intakes within 10---ft of this unit’s flue outlet
580J