Electrical requirements (cont.), Electrical hook-up – Bunn Dual TF DBC With Smart Funnel DUAL068000 User Manual
Page 5
Page 5
120/208 and 120/240 volt ac
single phase, 60 Hz models
Note: This electrical service consists
of 3 current carrying conductors
(Neutral, L1 and L2) and a separate
conductor for earth ground.
L2
N
L1
G
L2 RED
WHITE
GREEN
GREEN
NEUTRAL
L1 BLACK
L2 RED
WHITE
NEUTRAL
L1 BLACK
200 and 230 volt ac
single phase, 60 Hz models
Note: This electrical service
consists of 2 current carrying
conductors (L1 and L2) and a
separate conductor for earth
ground.
ELECTRICAL REQUIREMENTS (cont.)
L2 RED
200 or
230V
GREEN
L1 BLACK
GREEN
35058.2 022410
ELECTRICAL HOOK-UP
WARNING – If brewer is equipped with a power cord and it is ever damaged, it must be replaced by the manu-
facturer or authorized service personel with a special cord available from the manufacturer or its authorized
service personel in order to avoid a hazard. Improper electrical installation will damage electronic components.
Damage caused by incorrect electrical connections is not covered by warranty.
1. An electrician must provide electrical service.
2. Using a voltmeter, check the voltage and color coding of each conductor at the electrical source.
NOTE - Brewers shipped with a power cord are shipped without a plug on it. Qualified service personnel
must select and install the proper UL listed grounding type attachment plug specified on the rear of the
brewer.
3. Install the specified plug on the attached power cord.
4. Remove the access panel beneath the sprayheads to gain access to the terminal block.
5. Brewers not equipped with a power cord, feed the wire through the strain relief and connect it to the termi-
nal block.
6. Using the above diagrams, connect the desired electrical service to the field wiring terminal block.
7. If wiring the machine for operation on 120/208 or 120/240 volts with a Power Supply Cord, the Power
Supply Cord must be UL Listed Flexible Cord Type SO, SJO, SJTO, HSJO or SJOW, No. 12 AWG, 4 Con-
ductor, Rated 90° C. Attachment Plug Cap must be UL Listed, NEMA 14-20P or L14-20P Configuration,
Rated 125/250V, 20 AMPS. The Power Supply Cord must be at least 3 feet long and maximum 6 feet long
(measured from Strain Relief to end of the Attachment Plug Cap).
8. Connect the brewer to the power source and verify the voltage at the terminal block before proceeding.
9. Set toggle switch on component bracket to the appropriate position and replace the access panel.
10. If plumbing is to be hooked up later be sure the brewer is disconnected from the power source. If plumb-
ing has been hooked up, the brewer is ready for Initial Set-Up.
WARNING – Electrical connections must be made as specified above. Failure to follow these instructions can
result in personal injury, property or equipment damage.