B&B Electronics DELTA Temperature Controller DTB Series User Manual
Page 13
12
16
Mounting
Mounting Method
Mounting Bracket Installation
CT Wiring Method (if CT function is selected)
Step 1 : Insert the controller through the panel cutout.
Step 2 : Insert the mounting bracket into the mounting groove at the top and
bottom of the controller
Step 3 : Push the mounting bracket forward until the bracket stops at panel
wall.
Step 4 : Insert and tighten screws on bracket to secure the controller in place.
(The screw torque should be 0.8kgf-cm to 1.5kgf-cm)
DTB4824 Mounting Method:
DTB4848/4896/9696 Mounting Method:
1
3
2
06
.8m
m
M
ax
.
17
Error Acknowledge and Display
Communication error code response description:
Error status 102EH/4750H
PV read back 1000H/4700H
Error status
0001H
N/A
PV unstable
0002H
8002H
Re-initial, No temperature at this time
0003H
8003H
Input sensor did not connect
0004H
8004H
Input signal error
0005H
N/A
Over input range
0006H
8006H
ADC fail
0007H
N/A
EEPROM read/write error
Display message:
Power ON
Normal display
PV
DTB series, Firmware V1.50
Present value
SV
Output VR type with Event option
Set value
Sensor didn’t connect
Input error
PV
No
Error
SV
Connect
Input
EEPROM error
Input over range
PV
Error
PV flash when over
SV
EEPROM