LEGEND AND NOTES FOR TABLES 2A AND 2B

LEGEND

*Heaters are field installed only.

†Used to determine minimum disconnect per NEC.

**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v and

575 v. If power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly.

††Fuse or HACR circuit breaker.

||Optional disconnect switch is unavailable. (Applies to units with an FLA greater

or equal to 80.)

NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percentage of voltage
imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT:

If the supply voltage phase imbalance is more than 2%, con-

tact your local electric utility company immediately.

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor-Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor-Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

% Voltage Imbalance = 100 x

7

457