TROUBLESHOOTING

TROUBLESHOOTING

Problem

Cause

Correction

Supervised loads (air conditioner,
etc.) are not operating when
generator is supplying power

1.

AC1A-AC2B contacts not
operating correctly.

2.

Too much load on generator.

3.

Current transformer not
connected.

4.

Broken current transformer.

5.

Status LED stays lit constantly.

1A. Check AC1A-AC2B contacts for

proper operation.

B. Check control wiring to external

load.

C. Check harness between boards is

properly connected.

D. Check that there is 24 VAC to one

of the terminals.

E. Be sure 5 minute lock out has

elapsed.

F.

Be sure air conditioner start time
delay has elapsed.

2.

Decrease load to generator.

3.

Connect current transformer.

4.

Replace current transformer.

5.

Contact an authorized service
center.