10

MAINTENANCE

I. LUBRICATION

The outdoor fan motor is factory lubricated and requires no
oil.

II. COMPRESSOR

The compressor contains factory oil charges; replace oil when
lost. See Tables 1A and 1B for oil recharge. Recommended oil
is Sontex 200LT for all units.

III. CLEANING COILS

Coil should be washed out with water or blown out with com-
pressed air. Note that the blow-thru design causes dirt and
debris to build up on the inside of the coils.

Clean coil annually or as required by location and outdoor
air conditions. Inspect coil monthly and clean as required.
Fins are NOT continuous through coil sections. Dirt and
debris may pass through the first section, become trapped
between the rows of fins, and restrict condenser airflow. Use
a flashlight to determine if dirt or debris has collected
between coil sections. Clean coil as follows:

1. Turn off unit power.

2. Use a garden hose or other suitable equipment to

flush coil from the outside to remove dirt. Be sure to
flush all dirt and debris from drain holes in the base
of unit. Fan motors are waterproof.

Table 6A — Required Liquid Line Temperature (F) — English (At Service Valve)

Table 6B — Required Liquid Line Temperature (C) — SI (At Service Valve)

WARNING: Before performing recommended main-

tenance, be sure unit main power is off. Failure to do so
may result in electrical shock or injury from rotating fan
blades.

REQUIRED

SUBCOOLING

(F)

LIQUID PRESSURE AT SERVICE VALVE (PSIG)

134

141

148

156

163

171

179

187

196

205

214

223

233

243

253

264

274

285

297

309

321

331

346

359

0

76

79

82

85

88

91

94

97

100

103

106

109

112

115

118

121

124

127

130

133

136

139

142

145

5

71

74

77

80

83

86

89

92

95

98

101

104

107

110

113

116

119

122

125

128

131

134

137

140

10

66

69

72

75

78

81

84

87

90

93

96

99

102

105

108

111

117

120

123

126

129

129

132

135

15

61

64

67

70

73

76

79

82

85

88

91

94

97

100

103

106

109

112

115

118

121

124

127

130

20

56

59

62

65

68

71

74

77

80

83

86

89

92

95

98

101

104

107

110

113

116

119

122

125

25

51

54

57

60

63

66

69

72

75

78

81

84

87

90

93

96

99

102

105

108

111

114

117

120

REQUIRED

SUBCOOLING

(C)

LIQUID PRESSURE AT SERVICE VALVE (PSIG)

911

969 1030 1061 1121 1186 1219 1286 1360 1397 1471 1547 1588 1671 1755 1800 1885 1976 2026 2125 2222 2264 2379 2475

0

24

26

28

29

31

33

34

36

38

39

41

43

44

46

48

49

51

53

54

56

58

59

61

63

2

22

24

26

27

29

31

32

34

36

37

39

41

42

44

46

47

49

51

52

54

56

57

59

61

4

20

22

24

25

27

29

30

32

34

35

37

39

40

42

44

45

47

49

50

52

54

55

57

59

6

18

20

22

23

25

27

28

30

32

33

35

37

38

40

42

43

45

47

48

50

52

53

55

57

8

16

18

20

21

23

25

26

28

30

31

33

35

36

38

40

41

43

45

46

48

50

51

53

55

10

14

16

18

19

21

23

24

26

28

29

31

33

34

36

38

39

41

43

44

46

48

49

51

53

12

12

14

16

17

19

21

22

24

26

27

29

31

32

34

36

37

39

41

42

44

46

47

49

51

14

10

12

14

15

17

19

20

22

24

25

27

29

30

32

34

35

37

39

40

42

44

45

47

49