Bryant 538J-18-1 User Manual
Page 10
—
10
—
MAINTENANCE
I. LUBRICATION
The outdoor fan motor is factory lubricated and requires no
oil.
II. COMPRESSOR
The compressor contains factory oil charges; replace oil when
lost. See Tables 1A and 1B for oil recharge. Recommended oil
is Sontex 200LT for all units.
III. CLEANING COILS
Coil should be washed out with water or blown out with com-
pressed air. Note that the blow-thru design causes dirt and
debris to build up on the inside of the coils.
Clean coil annually or as required by location and outdoor
air conditions. Inspect coil monthly and clean as required.
Fins are NOT continuous through coil sections. Dirt and
debris may pass through the first section, become trapped
between the rows of fins, and restrict condenser airflow. Use
a flashlight to determine if dirt or debris has collected
between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Use a garden hose or other suitable equipment to
flush coil from the outside to remove dirt. Be sure to
flush all dirt and debris from drain holes in the base
of unit. Fan motors are waterproof.
Table 6A — Required Liquid Line Temperature (F) — English (At Service Valve)
Table 6B — Required Liquid Line Temperature (C) — SI (At Service Valve)
WARNING: Before performing recommended main-
tenance, be sure unit main power is off. Failure to do so
may result in electrical shock or injury from rotating fan
blades.
REQUIRED
SUBCOOLING
(F)
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
134
141
148
156
163
171
179
187
196
205
214
223
233
243
253
264
274
285
297
309
321
331
346
359
0
76
79
82
85
88
91
94
97
100
103
106
109
112
115
118
121
124
127
130
133
136
139
142
145
5
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125
128
131
134
137
140
10
66
69
72
75
78
81
84
87
90
93
96
99
102
105
108
111
117
120
123
126
129
129
132
135
15
61
64
67
70
73
76
79
82
85
88
91
94
97
100
103
106
109
112
115
118
121
124
127
130
20
56
59
62
65
68
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125
25
51
54
57
60
63
66
69
72
75
78
81
84
87
90
93
96
99
102
105
108
111
114
117
120
REQUIRED
SUBCOOLING
(C)
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
911
969 1030 1061 1121 1186 1219 1286 1360 1397 1471 1547 1588 1671 1755 1800 1885 1976 2026 2125 2222 2264 2379 2475
0
24
26
28
29
31
33
34
36
38
39
41
43
44
46
48
49
51
53
54
56
58
59
61
63
2
22
24
26
27
29
31
32
34
36
37
39
41
42
44
46
47
49
51
52
54
56
57
59
61
4
20
22
24
25
27
29
30
32
34
35
37
39
40
42
44
45
47
49
50
52
54
55
57
59
6
18
20
22
23
25
27
28
30
32
33
35
37
38
40
42
43
45
47
48
50
52
53
55
57
8
16
18
20
21
23
25
26
28
30
31
33
35
36
38
40
41
43
45
46
48
50
51
53
55
10
14
16
18
19
21
23
24
26
28
29
31
33
34
36
38
39
41
43
44
46
48
49
51
53
12
12
14
16
17
19
21
22
24
26
27
29
31
32
34
36
37
39
41
42
44
46
47
49
51
14
10
12
14
15
17
19
20
22
24
25
27
29
30
32
34
35
37
39
40
42
44
45
47
49