Bryant PURON 583B User Manual

Page 9

background image

—9—

BASE UNIT DIMENSIONS — 583B024-036

REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall

system, then the system performance may be compromised.

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue panel . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914.4)

NEC REQ’D CLEARANCES. in. (mm)

Between units, power entry side

. . . . . . . . . . . . . . 42 (1066.8)

Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . . 42 (1066.8)

LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. [MM]

“A”

CENTER OF GRAVITY

IN. [MM]

lb.

kg.

X

Y

Z

583B024040/060

208/230-1-60

290

131.5

37.02 [940.3]

22.0 [558.8]

14.5 [368.3]

16.0 [406.4]

583B030040/060

208/230-1-60
208/230-3-60

313

142.0

39.02 [991.1]

22.0 [558.8]

15.3 [387.4]

17.6 [447.0]

583B036060/090

208/230-1-60
208/230-3-60

460-3-60

321

145.6

35.02 [889.5]

22.0 [558.8]

15.3 [387.4]

16.5 [419.1]