Bryant 558F User Manual

Page 17

background image

17

2. Locate the minimum position (MIN POS) potentiome-

ter. Turn the potentiometer full CCW to fully close the
outdoor air dampers. Turn the potentiometer gradu-
ally clockwise (CW) to the desired position. See Fig. 17.

3. Replace the filter access panel. See Fig. 19. Ensure

the filter access panel is securely engaged.

4. Calculate the minimum airflow across the

EconoMi$er.

a. Calculate % of outside air using the following

formula.

% Outdoor air through EconoMi$er

b. Multiply total CFM by percentage outdoor air,

this gives outdoor air volume in CFM.

IX. STEP 9 — INSTALL ALL ACCESSORIES

After all the factory-installed options have been adjusted,
install all field-installed accessories. Refer to the accessory
installation instructions included with each accessory.

A. Motormaster® I Control (–20 F) Installation (558F180 and
210 Only)

Install Field-Fabricated Wind Baffles

Wind baffles must be field-fabricated for all units to ensure
proper cooling cycle operation at low ambient temperatures.

See Fig. 26 for baffle details. Use 20-gage, galvanized sheet
metal, or similar corrosion-resistant metal for baffles. Use
field-supplied screws to attach baffles to unit. Screws should
be

1

/

4

-in. diameter and

5

/

8

-in. long. Drill required screw holes

for mounting baffles.

Install Motormaster I Controls

One Motormaster I control is required on size 180 and 210
units. The Motormaster I control must be used in conjunction
with the Accessory Fan Motor Sequencing Kit and Winter
Start Kit (purchased separately). The Motormaster I device
controls outdoor fan no. 1 while outdoor fans no. 2 and 3 are
sequenced off by the Accessory Fan Motor Sequencing Kit.

Accessory Fan Motor Sequencing Kit — Install the Accessory
Fan Motor Sequencing Kit per instruction supplied with
accessory (purchased separately).

Winter Start Time Delay Relay Kit — Install the kit per the in-
structions supplied with the accessory (purchased separately).

Sensor Assembly — Install the sensor assembly in the loca-
tion shown in Fig. 27.

Motor Mount — To ensure proper fan height, replace the
existing motor mount with the new motor mount provided
with accessory.

% Outdoor
air

=

Mixture Temp – Return Air Temp
Outdoor Temp – Return Air Temp

WARNING: Personal Injury Hazard. Avoid possi-

ble injury by keeping fingers away from damper blades.

CAUTION: To avoid damage to the refrigerant

coils and electrical components, use recommended
screw sizes only. Use care when drilling holes.

20 mA LED

1k ohm Potentiometer

2 to 10 VDC at

0 to 2000 ppm

CO2 Sensors:

Rem ote

M inim um Position

Rem ote

LED

Outdoor Air Enthalpy

CROUTENT001A00

Return Air Enthalpy

CRRETENT001A00

Line

Voltage

CO
CO
COM
DAT
COM
REM
POT
COM
LED
COM

2
2

OAT
COM
OAH
+15V
RAT
COM
RAH
+15V

C

O

M PW

O

U

T T

T

Violet

C

O

M PW

O

U

T T

T

Violet

Field-supplied W iring

W iring Included

470 ohm

5 watt

Resistor

24 VAC m ust be present

on BI for the system to be

unoccupied.

Unoccupied Control

(Part num ber on the control

m ust be AD-DM E1701-1

or AD-DM E1711-1.)

Unoccupied

Contact

Tan
Violet
W hite
Red

Tan
Violet
W hite
Red

24 V

A

C

20 V

A

NOT

USED

1

2

-

(+)

CRCDXSEN004A00

Fig. 25 — Typical EconoMi$er Sensor Wiring