CONTROLS

OPERATING SEQUENCE
Cooling

1. Thermostat calls for cooling.

a. Indoor (evaporator) fan relay is energized and starts

evaporator fan.

b. Compressor contactor is energized to start compressor

and condenser fan (up to a 5-minute delay on single-
phase units).

2. When room thermostat is satisfied, the evaporator fan, com-

pressor, and condenser fan shut off.

Continuous Fan Operation — The thermostat can be set for
continuous operation by setting the fan switch to ON.

ELECTRICAL DATA

LEGEND

*Optional evaporator-fan motor nameplate data.

ELECTRIC HEATER DATA

LEGEND

*May be field converted to single-phase units, see electric heat installa-

tion instructions.

NOTE: Separate power source is required for all heaters. Control from
base unit 502A (24 v).

UNIT
502A

V-PH

(60 Hz)

VOLTAGE RANGE

COMPRESSOR

FAN MOTORS

POWER SUPPLY

Evaporator

Condenser

Min Ckt

Amps

MOCP

Amps

Min

Max

RLA

LRA

Hp

FLA

Hp

FLA

024

230-1

207

254

11.5

62.5

.17

1.10

.50

3.40

19.1

25

036

230-1

207

254

17.2

96.0

.50

3.20

.75

6.06

29.5

40

208/230-3

187

254

10.2

77.0

.50

3.20

.75

3.93

19.9

25

460-3

414

508

4.3

37.0

.50

1.50

.75

1.97

8.8

15

048

230-1

207

254

23.7

129.0

.75

4.00

1.0

8.35

42.0

60

208/230-3

187

254

13.5

99.0

.75

4.00

1.0

3.93

24.8

35

460-3

414

508

7.4

49.5

.75

2.15

1.0

1.97

13.4

15

575-3

518

632

5.8

40.0

.75

1.40

1.0

1.45

10.1

15

048*

208/230-3

187

254

13.5

99.0

1.5

5.60

1.0

3.93

26.4

35

460-3

414

508

7.4

49.5

1.5

2.80

1.0

1.97

14.0

20

060

230-1

207

254

28.8

169.0

.75

4.00

1.5

9.50

49.5

70

208/230-3

187

254

17.3

123.0

.75

4.00

1.5

4.82

30.4

45

460-3

414

508

9.0

62.0

.75

2.15

1.5

2.41

15.8

25

575-3

518

632

7.1

50.0

.75

1.40

1.5

1.90

12.2

20

060*

208/230-3

187

254

17.3

123.0

1.5

5.60

1.5

4.82

32.0

40

460-3

414

508

9.0

62.0

1.5

2.80

1.5

2.41

16.5

25

HACR — Heating, Air Conditioning, and Refrigeration
Hp

Horsepower

FLA

Full Load Amps

LRA

Locked Rotor Amps

MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA

Rated Load Amps

ELECTRIC HEATER

UNIT 88EN

USED WITH

UNIT 502A

V-PH

(60 Hz)

CAP. (kW)

BRANCH CIRCUIT

Heater Amps

MCA

MOCP (Amps)

0050CA01

024, 036

1-Stage Heat

240-1

5.0

20.8

26.0

30

0075CA01

240-1

7.5

31.3

39.1

40

0115CA01

240-1

11.5

47.9

59.9

60

0075EA01

208-3

5.6

15.6

19.5

20

240-3

7.6

18.0

22.6

25

1150EA01

208-3

11.3

31.2

39.0

40

240-3

15.0

36.1

45.1

50

0100EA01

048, 060

2-Stage Heat

208-3

7.5

20.8

26.0

30

240-1*

10.0

41.7

52.1

60

240-3

10.0

24.1

30.1

35

0150EA01

208-3

11.3

31.2

39.0

40

240-1*

15.0

62.5

78.1

80

240-3

15.0

36.1

45.1

50

0200EA01

208-3

15.0

41.7

52.1

60

240-1*

20.0

83.3

104.2

110

240-3

20.0

46.9

58.6

60

0300EA01

208-3

22.5

62.5

78.2

80

240-3

30.0

72.2

90.2

100

0300CA01

240-1

30.0

124.0

155.0

175

0100FA01

480-3

10.0

12.0

15.0

15

0150FA01

480-3

15.0

18.1

22.6

25

0200FA01

480-3

20.0

24.1

30.1

35

0300FA01

480-3

30.0

36.1

45.1

50

MCA

Minimum Circuit Ampacity

MOCP — Maximum Overcurrent Circuit Protection

(Fuses or Circuit Breaker)