Baldor TS250 User Manual
Page 38
4-16 Operation
MN2417
Continued
Cooling time
Runtime of the unloaded gen−set to cool the engine before stop.
Step: 1s; Range: 0 − 3600 s
AfterCoolTime
Runtime of engine after cooling pump. Binary output Cooling pump is
closed when the engine starts and opens AfterCool time delayed after
gen−set stops. Step: 1s Range: 0 − 3600s
CoolingSpeed
Selects the function of the Binary output IDLE/NOMINAL during engine
Cooling state.
NOMINAL : Cooling is executed at Nominal speed and generator
protections are active.
IDLE: Cooling is executed at Idle speed and generator protections are
switched off.
Hint: Binary output IDLE/NOMINAL must be configured and connected to
speed governor. Engine Idle speed must be adjusted on speed governor.
D+ function
ENABLED: The D+ terminal is used for both functions “running engine”
detection and charge fail detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only
DISABLED: The D+ terminal is not used.
Note: Magnetization current is independent of this setpoint value.
Table 4-11 Engine Protect Setpoints
ECUFreqSelect
This setpoint should be used only for Volvo and Scania engines.
ECU Speed Adjust
This setpoint should be used only for Volvo and Scania engines.
WTBF Accept RPM
The WtBfAcceptRPM delay setpoint will start to count down since
cranking. Controller waits before communicating with the ECU for this
time. This is because the JD engine passes some erroneous RPM signals
during the first 500ms. Step: 0,1s Range: 0 − 3s
Eng prot del
During the start of the gen−set, some engine protections have to be
blocked (e.g. Oil pressure). The protections are unblocked after the
Protection del time. The time starts after reaching Start RPM.
Step: 1s; Range: 0 − 300 s
Horn timeout
Max time limit of horn sounding. Set to zero if you want to leave the output
HORN open. Step: 1s; Range: 0 − 600 s
Overspeed
Threshold for over speed protection.
Step: 1% of nominal RPM; Range: 100 − 150%
Wrn Oil press
Warning threshold level for ANALOG INPUT 1.
Step: 1 psi; Range: Sd Oil press − 10000
Sd Oil press
Shutdown threshold level for ANALOG INPUT 1.
Step: 1 psi; Range: −100 − Wrn Oil press
Oil press del
Delay for ANALOG INPUT 1. Step: 1 s; Range: 0 − 180
Sd Water temp
Warning threshold level for ANALOG INPUT 2.
Step: 1 °C; Range: Wrn Wtemp − 10000
Wrn Water temp
Warning threshold level for ANALOG INPUT 2.
Step: 1 °F; Range: Wrn Wtemp low − Sd Water temp
Wrn Wtemp low
Warning threshold level for low value on ANALOG INPUT 2.
Step: 1 °F; Range: −100 − Wrn Water temp
Water temp Low del
Delay for ANALOG INPUT 2 Wrn Wtemp low. Step: 1 s; Range:1−180 s
Water temp del
Delay for ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 − 180 s
Wrn Fuel Level
Warning threshold level for ANALOG INPUT 3.
Step: 1 %; Range: Sd Fuel Level − 10000
Sd Fuel Level
Shutdown threshold level for ANALOG INPUT 3.
Step: 1 %; Range: −100 − Wrn Fuel Level
Fuel Level del
Delay for ANALOG INPUT 3. Step: 1 s; Range: 0 − 180 s
Batt overvolt
Warning threshold for high battery voltage.
Step: 0,1 V; Range: Batt undervolt − 40V
Batt undervolt
Warning threshold for low battery voltage.
Step: 0,1 V; Range: 8V − Batt overvolt
Batt volt del
Delay for low battery voltage alarm. Step: 1s; Range: 0 − 600 s
NextServTime
Counts down when engine running. If reaches zero, an alarm appears.
Step: 1h; Range: 0 −65535h