4-12 Operation
MN2417
Alarms
Following alarms are available:
Sensor fail (FLS) see Table 4-5
Sensor fail is detected when measured value is 6% out of selected sensor characteristic.
Sensor fail is indicated by ##### symbol instead measured value.
Warning (WRN) see Table 4-5
When warning comes up, only alarm outputs and common warning output are closed.
Shut down (SD) see Table 4-5
When the shut−down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and
common shutdown output are closed. Active or not reset protection disables start.
Table 4-5 Possible Warnings
Events specification
Protection type
Wrn Oil press
WRN
Sd Oil press
SD
Wrn Water temp
WRN
Sd Water temp
SD
Wrn Wtemp Low
WRN
Wrn Fuel Level
WRN
Sd Fuel Level
SD
Battery voltage <, >
WRN
Battery flat
SD
Start fail
SD
Vgen <, >
SD
Vgen unbl
SD
Fgen <, >
SD
Igen unbl
SD
Overload
SD
RPM over
SD
RPM under
SD
PickupFault
SD
Stop fail
SD
WrnServiceTime
WRN
Emergency Stop
SD
ECU Common Warning
WRN
ECU Shutdown
SD