4-20 Operation
MN2408
Figure 4-6 Analog Fault Menu Loop Parameters
Fault Name
Input Analog
Type
Fault
E Enable
Setpoint Level
(Pick up)
Setpoint Level Action
S Shutdown
Alarm Latch
Y Yes
Bypass On
Start
Transient
Delay (Sec)
Type
E=Enable
D=Disable
(Pick-up)
(Drop-out)
S=Shutdown
A=Alarm
Y=Yes
N=No
Start
Y=Yes
Delay (Sec)
D=Disable
A=Alarm
N=No
Y=Yes
N=No
Under Voltage
AC Voltage
E*
S
Y
Y*
5.0
Under Frequency
AC Frequency E*
S
Y
Y*
5.0
Weak Battery
DC Voltage
E*
18.0
N/A
A*
Y
N*
3.0
Low Battery
Voltage
DC Voltage
E*
25.6
N/A
A*
N
N*
120.0
High Battery
Voltage
DC Voltage
E*
30.4
N/A
A*
N
N*
10.0
Low Engine Temp
Temp Sender
E*
95 °F
N/A
A*
Y
N*
5.0
High ENG Temp #1
Alarm
Temp Sender
E*
198 °F
N/A
A
Y
Y
2.0
High ENG Temp #2
Shutdown
Temp Sender
E*
206 °F
N/A
S
Y
Y
2.0
Low Oil Press #1
Alarm
Press Sender E*
30PSI
N/A
A
Y
Y*
2.0
Low Oil Press #2
Shutdown
Press Sender E*
20PSI
N/A
S
Y
Y*
2.0
* Indicates parameter is non-programmable.
Figure 4-7 Digital Fault Menu Loop Parameters
Fault Name
Input #
Action
S Shutdown
Alarm Latch
Y Yes
Polarity
O Open
Bypass On
Start
Transient
Delay (Sec)
S=Shutdown
A=Alarm
Y=Yes
N=No
O=Open
C=Close
Start
Y=Yes
Delay (Sec)
A=Alarm
N=No
C=Close
Y=Yes
N=No
Low Oil Pressure
1
S
-
O
Y
0.5
High ENG TEMP
2
S
-
O
Y
1.0
Batt Chgr Input Fail 3
A
Y
C
N
30.0
Low Fuel Level
4
A
N
C
N
0.1
Figure 4-8 Calibration Menu Loop Parameters
Parameter
Setting
Volts A-B
Zero XXX
XXXVAC
Volts A-B
Span XXX
XXXVAC
Volts B-C
Zero XXX
XXXVAC
Volts B-C
Span XXX
XXXVAC
Volts C-A
Zero XXX
XXXVAC
Volts C-A
Span XXX
XXXVAC
Volts A-N
Zero XXX
XXXVAC
Volts A-N
Zero XXX
XXXVAC
Volts B-N
Zero XXX
XXXVAC
Volts B-N
Zero XXX
XXXVAC
Volts C-N
Zero XXX
XXXVAC
Volts C-N
Zero XXX
XXXVAC
Current A
Zero XXX
XXXAAC
Current A
Span XXX
XXXAAC
Current B
Zero XXX
XXXAAC
Current B
Span XXX
XXXAAC
Current C
Zero XXX
XXXAAC
Current C
Span XXX
XXXAAC
Battery Voltage
Span XXX
XX.X VDC
Engine Temperature
XXX
XXX C/F
Oil Pressure
XXX
XXXX PSI/KPA