Special pipelines connection – Amcor UCHW-H24AF2 User Manual
Page 21
5
INSTALLATION & REPAIR GUIDE
Split Wall-Mounted air conditioner
Outer diameter of
copper pipe
Tightening torque
6.35(1/4")
9.52(3/8")
12.7(1/2")
15.88(5/8")
19.05(3/4")
Table 1
Torque based upon the wrench to be used
In case of the users purchasing the machine for quick
coupler,there is no need to do the air purging procedures
and the following pipeline connection procedures should
be adopted:
1.Remove the dust caps from the indoor and outdoor units,
and the connecting pipe.
2.Align the joint counter of connecting pipe with the proper
indoor and outdoor joint conic surfaces,tighten the connecting
nut manually.Then,make it secure with a wrench as shown
Fig. 6 ,applying to above torque Table 1.
3.Remove the two valve core caps from the outdoor unit.
4.Turn on the high and low pressure valve cores with an
socket wrench,then tighten the two valve core caps of the
outdoor unit (Fig.7).
5.Finally ,wrap the hot insulating cotton around the joints
of indoor and outdoor units.
1.Connecting pipe bending minimum radius parameters
(Table 2)
2.Quick coupler assembly and disassembly limit:
the assembly and disassembly times are inadvisably
more than 7.
*Notes on installation of quick coupler:
Fig.6
Fig.7
*Special pipelines connection
(it is suitable for quick coupler)
Strengthened tightening torque
160kgf.cm(63kgf.inch)
300kgf.cm(118kgf.inch)
500kgf.cm(197kgf.inch)
750kgf.cm(295kgf.inch)
1200kgf.cm(472kgf.inch)
200kgf.cm(79kgf.inch)
350kgf.cm(138kgf.inch)
550kgf.cm(216kgf.inch)
800kgf.cm(315kgf.inch)
1400kgf.cm(551kgf.inch)
Table 2 Minimum bending radius
Normial
diameter(mm)
Minimum bending
radius(mm)
cooling capacity
DN8(5/16")
DN10-12
(1/2")
80(3")
100(4")
2100~2300W
(7000~8000BTU)
2500~5100W
(9000~18000BTU)
6100~7000W
(22000~24000BTU)
150(6")
DN14-16
(5/8")
High pressure valve
Valve core cap
Low pressure valve
Quick coupler
(wrapping with insulating cotton)