Operating and Installation Instructions DTS Air Conditioner

08.2001

085 408 022

5

5 Installation

Instructions

WARNING: To avoid possible personal injury or property damage when the Air
Conditioner is to be mounted on door of cabinet, be sure that hinges will
support the added weight of Air Conditioner. Also be certain Air Conditioner
does not over-balance the electronic cabinet causing it to tip over when the
door is opened. Weight of the unit can be found on the ID plate. Use all
mounting holes to insure stability and efficient seal.

It is not necessary to remove the unit cover prior to installing the unit or setting it into
operation. The unit is operable immediately after applying the operating voltage.

5.1 Place the drilling template included in the scope of supply onto the outside

installation surface of the enclosure.

5.2 Drill the holes, and cut out the openings required for air transfer.

CAUTION:

Prevent steel filings from entering the switch cabinet.

5.3 Drive two stud bolts, included in the accessories, into both upper fixing points

next to the notice sticker with the instructions of the depth, at the backside of
the unit.

5.4 Place sealing strips around the cutouts of the enclosure.

5.5 Thread power and control leads through the air supply opening into the

enclosure.

5.6 Suspend the cooling unit on the enclosure by using the stud bolts.

5.7 Affix the cooling unit from the inside of the enclosure using the M6 bolts

included in the accessory package.

CAUTION:

The sealings have to be pressed to a thickness of 2mm / 0.08 inch.

5.8 Connect the cooling unit to the power supply.

5.9 An additional 5-core signal line is supplied on several units (circuit diagram,
supplement) and is used for wiring a door contact and floating contact that opens
whenever certain faults occur (e.g. excessive pressure in the cooling system, power
failure, cable breakage in the signal line). Max. load on contact: 5A.


CAUTION:
Both mains voltage and frequency must correspond to the ratings printed on
the cooling unit's ID plate. Work on electrical systems may only be carried out
by qualified personal, who are to observe the applicable safety regulations.