1.13 Resource Block Parameter List, Fieldbus Foundation
Parameter
Rel.
Index Description
Type Store Size
byte
RO /
R/W Min. Max. Default
ST_REV
1
Is .incremented .each .time .that .there .is .a .change .in .a .static .
parameter .in .the .physical .block .
Un-
signed .
16
SRC
RO
0
TAG_DESC
Tag .name .of .the .block . .This .parameter .must .be .unique .in .the .
configuration .
OCTET_
STRING
SRC
3
R/W
»«
STRATEGY
3
This .can .be .used .to .group .a .Function .Block . .It .is .a .user .sup-
plied .parameter .for .identification .purpose .
Un-
signed .
16
SRC
R/W
0
ALERT_kEY
4
Alert .keys
Un-
signed .
8
SRC
1
R/W
0
MODE_BLk
5
Block .running .mode
DS-69
Mix
4
*
1,1, .
17,16
BLOCk_ERR
6
Block .errors
BIT_
STRING
D
RO
0
RS_STATE
7
State .of .the .function .block .application .state .machine
Un-
signed .
8
D
1
RO
0
TEST_RW
8
Read/write .test .parameter .used .only .for .conformance .testing
DS-85
D
11 R/W
0 . .0
DD_RESOURCE
9
String .identifying .the .tag .of .the .resource .which .contains .the .
Device .Description .for .this .resource .
VISIBLE_
STRING
SRC
3
RO
» .»
MANUFAC_ID
10
Enumeration; .controlled .by .FF
Manufacturer .identification .number .- .used .by .an .interface .
device .to .locate .the .DD .file .for .the .resource .
Un-
signed .
3
SRC
4
RO
WIKA
DEV_TYPE
11
Manufacturer’s .model .number .associated .with .the .resource .- .
used .by .interface .devices .to .locate .the .DD .file .for .the .resource .
Un-
signed .
16
SRC
RO
0x00ec
DEV_REV
1
Manufacturer .revision .number .associated .with .the .resource .
- .used .by .an .interface .device .to .locate .the .DD .file .for .the .
resource .
Un-
signed .
8
SRC
1
RO
0x03
DD_REV
13
Revision .of .the .DD .associated .with .the .resource .- .used .by .an .
interface .device .to .locate .the .DD .file .for .the .resource .
Un-
signed .
8
SRC
1
RO
0x01
GRANT_DENY
14
Access .Permissions . .Options .for .controlling .access .of .host .
computer .and .local .control .panels .to .operating, .tuning .and .
alarm .parameters .of .the .block .
DS-70 SRC
R/W
0
hARD_TYPES
15
The .types .of .hardware .available .as .channel .numbers .
BIT_
STRING
SRC
RO
0
RESTART
16
1: .Run,
: .Restart .resource,
3: .Restart .with .defaults,
4: .Restart .processor
Allows .a .manual .restart .to .be .initiated . .Several .degrees .of .
restart .are .possible .
Un-
signed .
8
D
1
R/W
1
FEATURES
17
Used .to .show .supported .resource .block .options .
BIT_
STRING
SRC
RO
0
FEATURE_SEL
18
Used .to .select .resource .block .options .
BIT_
STRING
SRC
RW
0
CYCLE_TYPE
19
Identifies .the .block .execution .methods .available .for .this .
resource
BIT_
STRING
SRC
RO
0xC000
CYCLE_SEL
0
Used .to .select .the .block .execution .method .for .this .resource .
BIT_
STRING
SRC
**
0xC000
MIN_CYLCE_T
1
Time .duration .of .the .shortest .cycle .interval .of .which .the .
resource .is .capable .
Un-
signed .
3
SRC
4
RO
0
MEMORY_SIZE
Available .configuration .memory .in .the .empty .resource . .To .be .
checked .before .attempting .a .download .
Un-
signed .
16
SRC
RO
0
NV_CYCLE_T
3
Interval .between .writing .copies .of .NV .parameters .to .non-vola-
tile .memory . .Zero .means .never .
Un-
signed .
3
SRC
4
RO
0
FREE_SPACE
4
Percent .of .memory .available .for .further .configuration . .Zero .in .a .
preconfigured .resource .
Floating .
Point
D
4
RO
0 .0
FREE_TIME
5
Percent .of .the .block .processing .time .that .is .free .to .process .
additional .blocks .
Floating .
Point
D
4
RO
0 .0
ShED_RCAS
6
Time .duration .at .which .to .give .up .on .computer .writes .to .func-
tion .block .RCas .locations .
Un-
signed .
3
SRC
4
R/W
640000
ShED_ROUT
7
ms .time .duration .at .which .to .give .up .on .computer .writes .to .
function .block .ROut .locations .
Un-
signed .
3
SRC
4
R/W