Ai_transducer block parameter list, 8 .6 .diagnostic .parameters, 8 .7 .sensor .error .detection .parameters – WIKA T53 User Manual
Page 22

AI_TRANSDUCER Block Parameter List
.8 .6 .Diagnostic .parameters
Parameter
Rel.
Index
FF
Description
Type Store Size
byte
RO /
R/W Min. Max. Default
INPUT_FAULT_GEN
3
Input .malfunction: .Diagnosis .object .for .errors .that .con-
cern .all .values
.
0 .= . device .OK
Bit:
.
0 .= . Rj .error
.
1 .= . Hardware .error
. .– .4 .= . reserved
.5 .– .7 .= . manufacturer-specific
Un-
signed .
8
D
1
RO
0
INPUT_FAULT_1
4
Input .malfunction: .Diagnosis .object .for .errors .that .con-
cern .SV_1
.
0 .= . Input .OK
Bit:
.
0 .= . underrange
.
1 .= . overrange
.
.= . lead .breakage
.
3 .= . short .circuit
.4 .– .5 .= . reserved
.6 .– .7 .= . manufacturer-specific
Un-
signed .
8
D
1
RO
0
INPUT_FAULT_2
5
Input .malfunction: .Diagnosis .object .for .errors .that .con-
cern .SV_
.
0 .= . Input .OK
Bit .definition .see .INPUT_FAULT_1
Un-
signed .
8
D
1
RO
0
Rj_FAULT
43
Input .malfunction: .Diagnosis .object .for .errors .that .con-
cern .RJ .sensor .
.
0 .= . Input .OK
Bit:
.
0 .= . underrange
.
1 .= . overrange
.
.= . lead .breakage
.
3 .= . short .circuit
Un-
signed .
8
D
1
RO
0
hW_ERROR
6
Diagnostic .bit .value .indicating .hardware .status
.
0 .= . hardware .OK
Bit:
.
0 .= . Input .power .supply .error
.
1 .= . Input .initialisation .error
.
.= . Input .communication .error
.
3 .= . Internal .temperature .sensor .error
.
4 .= . Device .not .factory .calibrated
.5 .– .6 .= . reserved
.
7 .= . Watchdog .initiated .cold .start .occurred
Un-
signed .
8
D
1
RO
0
.8 .7 .Sensor .error .detection .parameters
Parameter
Rel.
Index
FF
Description
Type Store Size
byte
RO /
R/W Min. Max. Default
SENSOR_WIRE_ChECk_1
6
Enables .lead .breakage .and .short .circuit .detection .for .
Sensor .1 .
List .of .valid .values:
0 .= .Lead .breakage .and .short .circuit .detection .enable .
1 .= .Lead .breakage .detection .enable, .short .circuit . .
detection .disable .
.= .Lead .breakage .detection .disable, .short .circuit . .
detection .enable .
3 .= .Lead .breakage .and .short .circuit .detection .disable .
Un-
signed .
8
SRC
1
R/W
3
SENSOR_WIRE_ChECk_2
7
Enables .lead .breakage .and .short .circuit .detection .for .
Sensor . .
Valid .values: .see .SENSOR_WIRE_CHECK_1 .
Un-
signed .
8
SRC
1
R/W
3
SENSOR_WIRE_ChECk_Rj
44
Enables .lead .breakage .and .short .circuit .detection .for .
RJ .Sensor .
Valid .values: .see .SENSOR_WIRE_CHECK_1 .
Un-
signed .
8
SRC
1
R/W
3