beautypg.com

DuraVent Multi-fuel venting system UL 641 User Manual

Page 7

background image

7

desired (Figure 6):

A. Place the appliance according to
manufacturer’s instructions.

B. Connect the Pipe Adapter to back of stove
and attach sufficient pipe to penetrate Wall
Thimble and extend at least 6” beyond the
exterior wall. You may install the optional
House Shield as shown in Figure 6. The
House Shield is used to protect the exterior
wall from vent discharge. Attach a Square or
Round Horizontal Cap. The Round Horizontal
Cap can be swiveled to be directed away
from nearby objects (fence, plants, etc.),
but must still be pointing in a generally
downward direction. Important: Horizontal
Caps must be pointed in a generally
downward direction to insure rain and snow
do not enter the cap, and cause potential

Figure 2

Figure 3

12 INCHES

MINIMUM

APPLY HIGH

TEMPERATURE

SEALANT COMPLETELY

AROUND TOP EDGE OF

STORM COLLAR

SHINGLES OVERLAP ON

TOP EDGE OF FLASHING

TEE WITH

CLEAN-OUT

ADAPTER

CEILING

SUPPORT/

FIRESTOP

SPACER

ATTIC

INSULATION

SHIELD

PIPE

ADAPTER

12” MIN

damage to the appliance. Either vent Cap
should be at least 6” from the wall.

C. Follow the below listed NFPA 211 rule for
distance of exit terminal from windows and
openings:
NFPA 211 (2003 ed.) Section 10.4 Termination:
10.4.5 (1) The exit terminal of a mechanical
draft system other than a direct vent
appliance (sealed combustion system
appliance) shall be located in accordance
with the following:
(a) Not less than 3 ft (.91m) above any forced
air inlet located within 10 ft. (3m).
(b) Not less than 4 ft. (1.2m) below, 4 ft. (1.2m)

WARNINg

WARNINg: Do not install any insulation

or other material inside the Wall

Thimble. Doing so can create a fire

hazard. The Wall Thimble requires the

created air clearance from the pipe

in order to make a safe installation.

However, building insulation may be

installed around the outside of the Wall

Thimble

This manual is related to the following products: