Refrigeration installation – Comfort-Aire HTS Series Split System,Two Stage, 2-5 Tons User Manual
Page 19

19
Installation, Operation & Maintenance
HTS SERIES SPLIT SYSTEM
Heat Controller, LLC
Refrigeration Installation
Turn service valves full out CCW (see Table 5) and then turn 
back in one-half turn to open service ports. Add the required 
refrigerant so that the total charge calculated for the unit 
and line set is now in the system. Open the service valve 
fully counter clockwise so that the stem will backseat and 
prevent leakage through the schrader port while it is not in 
use. Start unit in the heating mode and measure superheat 
and subcooling values after 5 minutes of run time. See tables 
14a to 14d for superheat and sub-cooling values. Superheat 
is measured using suction temperature and pressure at the 
compressor suction line. Subcooling should be measured 
using the liquid line temperature immediately outside the 
compressor section cabinet and either the liquid line service 
valve pressure or the compressor discharge pressure. Note 
that different values from tables 14a to 14d will be obtained 
due to the pressure losses through the condenser heat 
exchanger. Adding refrigerant will increase sub-cooling 
while superheat should remain fairly constant allowing for a 
slight amount of hunting in TXV systems. This increase in 
subcooling will require 5 minutes or so of operation before it 
should be measured. After values are measured, compare to 
the chart and go to “FINAL EVALUATION.”
PARTIAL CHARGE METHOD
- Open service valve fully
counterclockwise and then turn back in one-half turn to open 
service port. Add vaporized (Gas) into the suction side of 
the compressor until the pressure in the system reaches 
approximately 60-70 psig (R-22 systems) or 100-120 psig 
(R-410A systems). Never add liquid refrigerant into the suction 
side of a compressor. Start the unit in heating and add gas 
to the suction port at a rate not to exceed fi ve pounds [2.27 
kg] per minute. Keep adding refrigerant until the complete 
charge has been entered. Superheat is measured using 
suction temperature and pressure at the compressor suction 
line. Subcooling should be measured using the liquid line 
temperature immediately outside the compressor section 
cabinet and either the liquid line service valve pressure or the 
compressor discharge pressure. Note that different values 
from tables 14a to 14d will be obtained due to the pressure 
losses through the condenser heat exchanger. Adding 
refrigerant will increase sub-cooling while superheat should 
remain fairly constant allowing for a slight amount of hunting 
in TXV systems. This increase in subcooling will require 5 
minutes or so of operation before it should be measured. After 
values are measured, compare to the chart and go to “FINAL 
EVALUATION.”
FINAL EVALUATION 
- In a split system, cooling subcooling values can be 
misleading depending on the location of the measurement. 
Therefore, it is recommended that charging be monitored in 
the heating mode. Charge should be evaluated by monitoring 
the subcooling in the heating mode. After initial check of 
heating sub-cooling, shut off unit and allow to sit 3-5 minutes 
until pressures equalize. Restart unit in the cooling mode and 
check the cooling superheat against Tables 14a to 14d. If 
unit runs satisfactorily, charging is complete. If unit does not 
perform to specifi cations the cooling TXV (air coil side) may 
need to be readjusted (if possible) until the cooling superheat 
values are met.
Checking Superheat and Subcooling
Determining Superheat:
1. Measure the temperature of the suction line at a point
near the expansion valve bulb.
2. Determine the suction pressure by attaching refrigeration
gauges to the suction schrader connection at the 
compressor.
3. Convert the pressure obtained in step 2 to saturation
temperature (boiling point) by using the pressure/
temperature conversion table on the gauge set.
4. Subtract the temperature obtained in step 3 from step 1.
The difference will be the superheat of the unit or the total 
number of degrees above saturation temperature. Refer 
to Tables 14a to 14d for superheat ranges at specifi c 
entering water conditions.
Determining Sub-Cooling:
1. Measure the temperature of the liquid line on the smaller
refrigerant line (liquid line) just outside of the cabinet. This 
location will be adequate for measurement in both modes 
unless a signifi cant temperature drop in the liquid line is 
anticipated.
2. Determine the condensor pressure (high side) by
attaching refrigerant gauges to the schrader connection 
on the liquid line service valve. If the hot gas discharge 
line of the compressor is used, refer to the appropriate 
column in Tables 14a to 14d.
3. Convert the pressure obtained in step 2 to the saturation
temperature by using the press/temp conversion table on 
the gauge set.
4. Subtract the temperature of Step 3 from the temperature
of Step 1. The difference will be the sub-cooling value for 
that unit (total degrees below the saturation temperature). 
Refer to Tables 14a to 14d for sub-cooling values at 
specifi c entering water temperatures.
