Troubleshooting form, R-410a, Hev/h series – Comfort-Aire HEH Series 2 to 5 Tons User Manual
Page 44

44
Installation, Operation & Maintenance
HEV/H SERIES
Heat Controller, LLC.
TROUBLESHOOTING FORM
COAX
COMPRESSOR
DISCHARGE
SUCTION
HWG
COOLING CYCLE ANALYSIS -
COAX
COMPRESSOR
DISCHARGE
SUCTION
HWG
HEATING CYCLE ANALYSIS -
PSI
SAT
PSI
SAT
°F
°F
AIR
COIL
°F
°F
FP2: HEATING
LIQUID LINE
°F
EXPANSION
VALVE
AIR
COIL
°F
°F
PSI
SAT
PSI
SAT
°F
°F
°F
°F
WATER IN
WATER OUT
PSI
PSI
°F
°F
WATER IN
WATER OUT
PSI
PSI
Heat of Extraction (Absorption) or Heat of Rejection =
________ flow rate (
diff. (
factor = _____________
(Btu/hr)
Superheat
Subcooling
Suction temperature - suction saturation temp.
Discharge saturation temp. - liquid line temp.
=
=
=
=
(deg F)
(deg F)
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.
†
Use 500 for water, 485 for antifreeze.
FLASH
GAS LINE
°F
FP1
SENSOR
°F
EXPANSION
VALVE
FP2: FLASH
GAS LINE
°F
OTHER SIDE
OF FILTR DR
°F
FP1: CLG
LIQ LINE
°F
Refrigerant Type
:
R22
gpm) x ________ temp.
deg. F) x ________ fluid
†
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis
using P/T ports to determine water flow and temperature difference. If water-side analysis shows
poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a
last resort.
R-410A