Comfort-Aire HEH Series 2 to 5 Tons User Manual
Page 16

16
Installation, Operation & Maintenance
HEV/H SERIES
Heat Controller, LLC.
Unit Power
Disconnect
Flow
Controller
Insulated
Hose Kit
P/T Plugs
Thermostat
Wiring
Air Pad or Extruded
polystyrene insulation
board
Figure 12: Typical Ground-Loop Application
GROUND-LOOP HEAT PUMP APPLICATIONS
GROUND-WATER HEAT PUMP APPLICATIONS
Open Loop - Ground Water Systems
Typical open loop piping is shown in Figure 14. Shut off 
valves should be included for ease of servicing. Boiler 
drains or other valves should be “tee’d” into the lines to 
allow acid flushing of the heat exchanger. Shut off valves 
should be positioned to allow flow through the coax via 
the boiler drains without allowing flow into the piping 
system. P/T plugs should be used so that pressure drop 
and temperature can be measured. Piping materials 
should be limited to copper or PVC SCH80. Note: Due to 
the pressure and temperature extremes, PVC SCH40 
is not recommended.
Water quantity should be plentiful and of good quality. 
Consult table 3 for water quality guidelines. The unit can 
be ordered with either a copper or cupro-nickel water 
heat exchanger. Consult Table 3 for recommendations. 
Copper is recommended for closed loop systems and 
open loop ground water systems that are not high 
in mineral content or corrosiveness. In conditions 
anticipating heavy scale formation or in brackish water, a 
cupro-nickel heat exchanger is recommended. In ground 
water situations where scaling could be heavy or where 
biological growth such as iron bacteria will be present, an 
open loop system is not recommended. Heat exchanger 
coils may over time lose heat exchange capabilities due 
to build up of mineral deposits. Heat exchangers must 
only be serviced by a qualified technician, as acid and 
special pumping equipment is required. Desuperheater 
coils can likewise become scaled and possibly plugged. 
In areas with extremely hard water, the owner should be 
informed that the heat exchanger may require occasional 
acid flushing. In some cases, the desuperheater option 
should not be recommended due to hard water conditions 
and additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality 
requirements. Scaling potential should be assessed using 
the pH/Calcium hardness method. If the pH <7.5 and the 
calcium hardness is less than 100 ppm, scaling potential 
is low. If this method yields numbers out of range of those 
listed, the Ryznar Stability and Langelier Saturation 
indecies should be calculated. Use the appropriate 
scaling surface temperature for the application, 150°F 
[66°C] for direct use (well water/open loop) and 
desuperheater; 90°F [32°F] for indirect use. A monitoring 
plan should be implemented in these probable scaling 
situations. Other water quality issues such as iron fouling, 
corrosion prevention and erosion and clogging should be 
referenced in Table 3.
13.
