Heater running but not heating, Start, Problem solved. problem solved – Aquacal T115 User Manual

Page 31

background image

31

START

Is the air being discharged

out of the top of the heater 9-12

degrees cooler than the

outside air?

START

Is the air being discharged

out of the top of the heater 9-12

degrees cooler than the

outside air?

Is the pool pump timer

set to allow extended

operation of the heater?

Is the pool pump timer

set to allow extended

operation of the heater?

Yes

Extend the pool pump's

hours of operation to

accommodate additional

heater run time required

in cooler conditions.

Extend the pool pump's

hours of operation to

accommodate additional

heater run time required

in cooler conditions.

Is the heater

performing

adequately?

Is the heater

performing

adequately?

Problem

Solved.

Problem

Solved.

No

Yes

Is the defrost light on, or

does the display read : "FS" ?

Is the defrost light on, or

does the display read : "FS" ?

No

Yes

The defrost light or "FS"

displayed indicates air

temperature may be too low

to support the heater's

operation. Heater will

remain in defrost until air

temperature rises.

The defrost light or "FS"

displayed indicates air

temperature may be too low

to support the heater's

operation. Heater will

remain in defrost until air

temperature rises.

Call AquaCal for

Assistance:

800-786-7751.

Call AquaCal for

Assistance:

800-786-7751.

No

Yes

No

Is the air Temp. above

40ºF (analog control)

or

38ºF (digital control)

?

Is the air Temp. above

40ºF (analog control)

or

38ºF (digital control)

?

Yes

No

Problem

Solved.

Problem

Solved.

Ambient

conditions too cold

to operate heater.

Ambient

conditions too cold

to operate heater.

Heater Running but Not Heating

Analog or Digital Controls - 12/22/03