PeratioN

Factory Settings

Range of Adjustment

Set Point

Operating Range†

Minimum Set Point

Maximum Set Point

Standard Cooler Setting

34º F

34º F to 39º F

33º F

35º F

White Wine

50º F

50º F to 55º F

45º F

55º F

Red Wine

60º F

60º F to 65º F

55º F

65º F

Adjusting the factory set point will also adjust the operating range by the same amount

Models BB, ND, LP, FV, MFV, UCR Self Contained

Coolers using Dixell digital thermostat controller

The thermostat control probe wire connector

may become disconnected when the compressor

compartment cover and/or grill are removed. This

will result in thermostat P1 code. While the P1 code is

flashing the compressor will cycle 5 minutes on and 5

minutes off and may cause icing of the evaporator coil.

Service calls to reconnect the probe wiring are not

covered by factory warranty.

Probe wire

connector

The refrigerator is programmed to automatically

defrost four times daily for approximately twenty

minutes. During defrost, the fan inside the cooler

will remain on and the refrigeration system will

turn off. To initiate defrost manually, push and hold

the DEFROST button for more than two seconds.
The thermostat controller does not have an “OFF”

function. To turn refrigerator off, the unit must be

unplugged or power to the electrical branch circuit

has to be turned off via a circuit breaker or switch.

To change the set point - push and hold the SET

button for more than two seconds. When the º F

display begins flashing, push the up arrow or down

arrow buttons to adjust the set point to the desired

value.
To save the new set point and return to the tem-

perature display mode - push and release the SET

button or wait ten seconds.

The operating temperature range is preset at the

factory according to the table below and can be

adjusted up or down within the limits shown.
To see the set point - push and immediately release

the SET button. The set point will be displayed.
To return to normal visualization - Push and

immediately release the SET button or wait five

seconds.