List of functions: (xxxx = 125% f. s.)
Dialog item Value
Description
MENÜ
-1...9999 Primary display, e.g. the value selected in the DISP menu appears here
DISP
.....
Display value which should be permanently in the display:
act
actual measured value
sp1
switching point SP1
sp2
switching point SP2
max
maximum peak value
min
minimum peak value
ACT.
-1...9999 Display of actual measured value in bar
UNIT
Fixing
the
unit
bar
bar = bar
The unit is shown in the display appr.
psi
psi x = psi x 10
every 30 sec. for appr. 5 sec.
psi
psi = psi
HPa
HPa = Hekto-Pascal
mbar
mbar = millibar
UND
Unit display “on” or “off”
SP.1 .....
none
switching output deactivated
wind
window technology
stnd
standard evaluation SP2
erro
error output
ON-1
-1 ... xxxx
Switch-on point for SP1; if the ON value is smaller than the OFF
value
the switching point evaluation is falling
OFF-1
-1 ... xxxx
Switch-off point for SP1
DLY1
0,0s...9,9s
Switch-on / switch-off delay for SP1 in seconds
INV-1
.....
Inversion of switching output SP1
hlfs
high-level-fail-save (normally open function)
Ilfs
low-level-fail-save (normally closed function)
SP.2
.....
none
switching output deactivated
wind
window technology
stnd
standard
evaluation
SP2
erro
error output
ON-2
-1 ... xxxx
Switch-on point for SP2;
if the ON value is smaller than the OFF value
the switching point evaluation is falling
OFF-2
-1 ... xxxx
Switch-off point for SP2
DLY2
0,0s...9,9s
Switch-on / switch-off delay for SP2 in seconds
INV-2
-----
Inversion of switching output SP2
hlfs
high-level-fail-save (normally open function)
Ilfs
low-level-fail-save (normally closed function)
MAX
-1 ... xxxx
Display of peak value
CLRH
-----
Delete the maximum value memory
-----
no deletion
clr
delete
value
3
2
Dialog item
Value
Description
CDLY
0,0s...9,9s
Time setting to delete the maximum value memory after switching
point SP1 is reached (manual deletion is still possible)
MIN
-1 ... xxxx
Display of peak value “Min“
CLRL
-----
Delete the minimum value memory
----- no deletion
clr
delete
value
OFFS
-9,9 ...+xx
Measured value offset in bar
CUT
0,0 ... +xx
Cut-off. e.g. signal suppression at measuring range start in bar
DLDS
0,0 ... 9,9s
Time delay for currently displayed value in seconds
ERRC ----- Error
messages:
0:
-ok-
no error
1:
max
exceeding pos. measuring range
2:
min
exceeding neg. measuring range
3:
dig1
switching output 1 error
4:
dig2
switching output 2 error
5:
anao
analog output error
6:
sens
sensor error
7:
data
data error (EEProm)
8:
prog
program error
9:
cal
calibration error
V7.X
Lev0...Lev2 Programming lock indication (see code)
Version display with actual input level:
0 :
only display of operating parameters, no changes possible
1 :
only switching points can be set (“max” and “min” memories)
2 :
release user level (all operating parameters for customer)
LITH
20 ... 100
Change display brightness 20...100%
(only for units with Dot-Matrix display)
AOZS
0 ... 9999
Scale the analog output - start value (e. g. 0 bar = 4 mA)
AOFS
0 ... 9999
Scale the analog output - end value (e. g. 400 bar = 20 mA)
(output signal start value always corresponds to the display initial
value, e. g. 0 bar = 4mA)
Maximum turn-down 4 : 1, i.e. at values below 25 % of the
measuring range the analog output is switched off
CODE 000...999
Security
Sequence
Lev1: 471
Allow to change switching point parameters only
Lev2: 740
Able to reconfi gure all allowable parameters
Lev0: 999
All parameters will be lock
OPT
-----
For internal use only
(onlyV7.X)
For models shipped before Nov. 23, 2013