beautypg.com

Automation Components ACI/ACI RH Room Series User Manual

Page 2

background image

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562

PH: (608) 831-2585 FAX (608) 831-7407

I0000144.DOC REV 2

15 - 36 VDC or 21.6 - 26.4 VAC Input / 0 - 5 VDC Output

15 - 36 VDC Input / 4 - 20mA Output

15 - 36 VDC Supply Voltage

Figure # 4

15 - 36 VDC Supply Voltage or

21.6 - 26.4 VAC Supply Voltage

Supply Ground / Signal Common

0 - 5 VDC Output

Io

4 - 20mA Output

Io

4

Vin Gnd

Zero

Vo

6

5

S2

SW3

S1

SW2

3

2

4

3

1

ON

2

1

ON

Span

4

Vin Gnd

Zero

Vo

6

5

S2

SW3

S1

SW2

4

3

3

2

2

ON

1

1

ON

Span

18 - 36 VDC Supply Voltage or

21.6 - 26.4 VAC Supply Voltage

Supply Ground / Signal Common

0 - 10 VDC Output

4 - 20mA Output

21.6 - 26.4 VAC Supply Voltage

Supply Ground / Signal Common

ON

SW3

ON

SW3

21.6 - 26.4 VAC Input / 4 - 20mA Output

18 - 36 VDC or 21.6 - 26.4 VAC Input / 0 - 10 VDC Output

Gnd

Io Vin

Zero

Vo

6

5

4

3

4

SW2

ON

S1

2

1

3

2

Gnd

Io Vin

Zero

Vo

6

5

S1

4

4

3

SW2

ON

3

2

2

1

Span

S2

1

Span

S2

1

RH Test and Calibration Dip Switch Settings (See Figure #3)

Note: Do not adjust these switches unless you are using them to troubleshoot or recalibrate the sensor. Dipswitch #3
should always be left in the ON position. Failure to do so will not allow the RH transmitter to read the sensor (The
output will always remain the same).

0% RH Output - Transmitter always outputs a signal of 4 mA or 0 VDC. Sensor doesn’t affect the transmitter
output. (For Trouble Shooting Purposes Only)
50% RH Output - Transmitter always outputs a signal of 12 mA, 2.5 VDC, or 5 VDC. Sensor doesn’t affect the
transmitter output. (For Trouble Shooting Purposes Only)
100% RH Output - Transmitter always outputs a signal of 20 mA, 5 VDC, or 10 VDC. Sensor doesn’t affect the
transmitter output. (For Trouble Shooting Purposes Only)
Normal Operating Condition - The DIP switch must be set in this position for the RH signal to change, due to the
actual measurement of the Relative Humidity by the humidity sensor.
Increment RH Output - This DIP switch will allow you to calibrate the sensor through the software. The switch
must be toggled from the Off to the On position and then returned to the Off position for an
increase of 0.5% RH. This means that if your humidity has drifted 1% over a certain time
period, you will be able to toggle the Increment RH Output switch (2) times in order to

slide the whole curve upward 1%. Note: This is only a single point calibration, and is not

recommended for critical applications. Please contact the factory before doing any
field calibration.