Chapter 1: installation and assembly – Pathway MR Installers Guide User Manual
Page 4

DMXPathfinder LR
Installation & Assembly
3
Chapter 1: Installation and Assembly
S
UMMARY
This section describes how to correctly assemble the DMXPathfinder MR
hardware into an equipment rack and connect permanently installed external
wiring.
To ensure a trouble-free installation, you should follow this sequence:
1. Install the equipment rack
2. Run conduit and pull cable
3. Install auxiliary rack equipment and power bars
4. Mount termination boards (if applicable)
5. Dress cable in the rack and terminate (if possible)
6. Unpack the DMXPathfinder MR I/O Modules and prepare
7. Install the I/O Modules in the rack
8. Connect cabling to the I/O Modules
9. Power up and test
B
EFORE
S
TARTING
Before installing the DMXPathfinder MR equipment rack, you should carefully
consider the environment in which the equipment is to be installed, the
proximity to power sources, and the required conduit and/or cable runs.
Environmental Considerations -- To maximize equipment life and minimize
the possibility of unreliable operation or failures, the following conditions
should be adhered to:
• Ambient temperature extremes: -10 to 50 degrees C
• Recommended operating temperature: +10 to +40 degrees C
• Relative humidity: 10-95% non-condensing
• General conditions: clean, dust-free environment
Fan Cooling -- Each of the DMXPathfinder MR Output Modules is provided
with an internal cooling fan. These fans draw air in on the right hand side
and exhaust air on the left. To ensure adequate air circulation, do not block
the modules at either side. If more than two or three Output Modules are
installed in the same rack, allow for at least a 1U ventilation panel at the top
and bottom of the rack.