beautypg.com

Operation, Refrigerators, Freezers – Nor-Lake Undercounter Laboratory & Pharmacy Refrigerators & Freezers User Manual

Page 2

background image

OPERATION

REFRIGERATORS

FORCED AIR UNIT COOLER MODELS
The forced air under counter refrigerators employ a unit cooler evaporator located inside the cabinet

as the heat-removing source. Through the refrigeration process, heat is captured in the evaporator,

transferred to the condensing unit located at the bottom of the cabinet, and expelled to the

surrounding outside air. It is extremely important to maintain the minimum four-inch clearance from the

bottom of the cabinet to the floor for the refrigeration process to function properly. The cabinet

cannot be operated without the legs or casters installed.

During the operation of these units, frost will periodically form on the coil surface. Each time the

refrigeration compressor cycles to the "off" position, the evaporator fans and condenser fans will

continue to run. This will tend to keep the interior of the cabinet at a constant temperature and at the

same time remove any frost build up on the unit by circulating the inside air over the coil. The water

produced will collect in the unit cooler drain pan and travel down a drain tube to the condenser drain

pan where the water will vaporize back into the air.

The refrigeration system is designed to provide a 3.3°C temperature. The system employs a

"constant cut-in" control. This device accomplishes control of the interior by sensing the evaporator

coil. Since the control features a non-adjustable "cut-in" temperature of 3.3°C, and the sensor tube is

embedded in the fins of the evaporator coil, nuisance coil icing is eliminated because the controller

will not permit compressor start up until the coil reaches 3.3°C. Adjusting the control knob on this

system will adjust the "cut-out" temperature only. The control knob on the refrigerator is located on

the unit cooler front panel.

COLD WALL MODELS
Some of the under counter refrigerators are available in a cold wall version. The cold wall models

employ evaporator tubing embedded in the sidewalls, back, and top of the unit. During the

refrigeration process, heat is removed through the evaporator tubing and expelled through the

condensing unit. With this type of design, condensation may form on the interior of the cabinet and

should be periodically wiped dry. In order to assure proper airflow, make certain the flow of air

behind the cabinet and through the front louver is not restricted.

The refrigeration system on this cabinet uses a temperature thermostat that senses the cut in and

cut out temperatures of the cold wall evaporator coil. The temperature can be adjusted by turning the

thermostat control knob that is located behind the lower front panel.

FREEZERS

FORCED AIR UNIT COOLER MODELS
The forced air under counter freezers employ a unit cooler evaporator located inside the cabinet as

the heat-removing source. Through the refrigeration process, heat is captured in the evaporator,

transferred to the condensing unit located at the bottom of the cabinet, and expelled to the

surrounding outside air. It is extremely important to maintain the minimum four-inch clearance as

described in this manual under "Location" for the refrigeration process to function properly. The

cabinet cannot be operated without the legs or casters installed.

After shutting the door on these freezer models, a short amount of time must be allowed before the

door can be reopened. This is due to the tight seal maintained between the door and the cabinet.

Waiting a few moments for the pressure to equalize permits the door to be opened easily.