beautypg.com

Panasonic 36PEF1U6 User Manual

Page 128

background image

1-122

1. Specifications

1-14. LEAK TEST, EVACUATION AND

ADDITIONAL REFRIGERANT CHARGE

Perform an air-tightness test for this package A/C.

Check that there is no leakage from any of the
connections. Air and moisture in the refrigerant system
may have undesirable effects as indicated below.

pressure in the system rises

operating current rises
cooling (or heating) effi ciency drops

moisture in the refrigerant circuit may freeze and block

capillary tubing

water may lead to corrosion of parts in the refrigerant

system

Therefore, the indoor unit and tubing between the indoor
and outdoor unit must be leak tested and evacuated to
remove any noncondensables and moisture from the
system.

Air Purging with a Vacuum Pump (for Test Run)

Preparation

Check that each tube (both liquid and gas tubes) between
the indoor and outdoor units has been properly connected
and all wiring for the test run has been completed.
Remove the valve caps from both the gas and liquid
service valves on the outdoor unit. Note that both liquid
and gas tube service valves on the outdoor unit are kept
closed at this stage.

The refrigerant charge at the time of shipment is only

guaranteed suffi cient for a tubing length of up to 100 ft.
The tubing may exceed this length, up to the maximum
permitted length; however, an additional charge is
necessary for the amount that the tubing exceeds 100 ft.
(No additional refrigerating machine oil is needed.)

1. Leak Test

(1) With the service valves on the outdoor unit closed,

remove the 1/4 in. fl are nut and its bonnet on the gas
tube service valve. (Save for reuse.)

(2) Attach a manifold valve (with pressure gauges) and

dry nitrogen gas cylinder to this service port with
charge hoses.

CAUTION

Use a manifold valve for air
purging. If it is not available,
use a stop valve for this
purpose. The “Hi” knob of the
manifold valve must always be
kept closed.

Fig. 1-123

Fig. 1-122

Fig. 1-124

Manifold valve

Pressure
gauge

Lo

Hi

Charge hose

Outdoor unit

Liquid
tube

Gas
tube

Nitrogen gas cylinder
(In vertical standing
position)

Close

Close

Open

Cylinder
valve

Outlet
Inlet

Vacuum pump

Manifold gauge

1

SM830203-01_PAC-i_US-letter.indb122 122

SM830203-01_PAC-i_US-letter.indb122 122

2012/01/19 22:39:36

2012/01/19 22:39:36