SPECIFICATIONS
-Performance/Size/Weight-
-Water/Electrical Requirements-
155 - Heating Only Models
155AHDE
155BHDE
155DHDT
155GHDE
BTU - 80%RH
Air ºF / Water ºF…80/80
127,000
127,000
110,000
127,000
COP 6.3
6.3
6.3
6.3
Voltage/Hz/Phase 208-230/60/1
200-230/60/3
380-415/50/3
460/60/3
Min. Circuit Ampacity
37
30
15.22
15.22
Max. Fuse or Breaker
60
50
25
25
Rec. Fuse or Breaker
40
40
20
20
Min-Max Water Flow (gpm)
20-70 20-70
20-70 20-70
Shipping weight (lbs)
430
430
430
430
Shipping Size (l x w x h)
40” x 37” x 47”
40” x 37” x 47” 40” x 37” x 47”
40” x 37” x 47”
Uncrated Weight (lbs)
403
403
403
403
Uncrated Size (l x w x h)
37” x 33” x 41”
37” x 33” x 41”
37” x 33” x 41”
37” x 33” x 41”
155 - Heat & Cool Models (Reversing)
155ARDE
155BRDE
155DRDT
155GRDE
BTU - 80%RH
Air ºF / Water ºF…80/80
120,000
120,000
105,000
105,000
COP 6.1
6.1
5.9
5.9
Voltage/Hz/Phase 208-230/60/1
208-230/60/3
380-415/50/3
460/60/3
Min. Circuit Ampacity
37
30
15.22
15.22
Max. Fuse or Breaker
60
50
25
25
Rec. Fuse or Breaker
40
40
20
20
Min-Max Water Flow (gpm)
20-70 20-70
20-70 20-70
Shipping weight (lbs)
430
430
430
430
Shipping Size (l x w x h)
40” x 37” x 47”
40” x 37” x 47” 40” x 37” x 47”
40” x 37” x 47”
Uncrated Weight (lbs)
403
403
403
403
Uncrated Size (l x w x h)
37” x 33” x 41”
37” x 33” x 41”
37” x 33” x 41”
37” x 33” x 41”