Warning – Alliance Laundry Systems Stacked Clothes Dryer User Manual
Page 41
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Installation
39
510975
Figure 26
.
Figure 27
H318I
1
NOTE: Where the exhaust duct pierces a
combustible wall or ceiling, the opening must be
sized per local codes.
3
Clearance per Local Codes
4
No Screen or Cap
5
Clean Out Cover – Inspect Monthly
2
Wall
HORIZONTAL EXHAUST INSTALLATION
2
3
4
EXHAUST
OUTLET
1
A
B
C
D
E
F
G
H
I
J
K
AIR
FLOW
EXHAUST AIR FLOW
MAXIMUM LENGTH OF
DUCT 30 feet (9.1 m)
30°
5
H319I
1
Roof
2
Wall
3
2" (5 cm) Minimum
4
NOTE: Where the exhaust duct pierces a
combustible wall or ceiling, an opening must
be sized as shown or per local codes.
1
2
3
4
VERTICAL EXHAUST INSTALLATION
CONNECT TO DRYER
Duct Station
Minimum Diameter of
Collector Duct
A
4 inches (10.2 cm)
B
8 inches (20.3 cm)
C
9 inches (22.9 cm)
D
10 inches (25.4 cm)
E
11 inches (27.9 cm)
F
12 inches (30.5 cm)
G
13 inches (32.6 cm)
H
14 inches (35.6 cm)
I
15 inches (38.1 cm)
J
15 inches (38.1 cm)
K
16 inches (40.6 cm)
To reduce the risk of fire and the
accumulation of combustion gases, DO
NOT exhaust dryer air into a window well,
gas vent, chimney or enclosed,
unventilated area, such as an attic, wall,
ceiling, crawl space under a building or
concealed space of a building.
W045
WARNING