beautypg.com

Maintenance – Blodgett 40ES-KLT Series User Manual

Page 16

background image

14

OM-40ES-KLT

WARNING

TO AVOID INJURY, READ AND FOLLOW ALL

PRECAUTIONS STATED ON THE LABEL OF

THE WATER TREATMENT COMPOUND.

Maintenance

B. Jacket Vacuum/Removing Air from Jacket

When the kettle is cold, a positive pressure reading on the pressure/vacuum

gauge or a reading near zero indicates that there is air in the jacket. Air in the

jacket acts as an insulator, and slows kettle heating.

To remove air:

1. Start the unit. (Be sure there is water or product in the kettle when

heating).

2. When the pressure/vacuum gauge reaches a positive pressure reading of

five PSI, release the trapped air and steam by pulling up the safety valve

ring for about five seconds. Repeat this step three or four times. Then let

the pull ring snap back into the closed position.

3. If there is little discharge (mostly air), and the pressure gauge drops back

to zero PSI, allow the pressure to build back to five PSI and repeat the

procedure.

4. Once steam has been vented from the jacket as described in b, above,

remove the hot water from the kettle and replace it with cold. This will

condense steam in the kettle jacket, and the pressure gauge should

show a reading of 20 to 30 inches mercury (Hg) below zero. If it does not,

or if the vacuum is leaking down, contact an authorized service agency to

correct the problem.

C. Jacket Filling and Water Treatment

The jacket was charged at the factory with the proper amount of treated water.

You may need to restore this water, either because it was lost as venting

steam or by draining. If you are replacing water lost as steam, use distilled

water. If you are replacing treated water that ran out of the jacket, prepare

more treated water as directed in “Water Treatment Procedure,” below.

1. Allow the kettle to cool completely. The procedure will be easier with the

kettle under vacuum ( pressure gauge reading below zero).

2. Allow the kettle to cool completely. Remove the pipe plug from the jacket

fill assembly. Pour in the distilled or treated water. Using a funnel will

help you in this process. Hold the pressure relief valve open while you

pour, to let air escape from the jacket. Continue adding water until the

water level rises to the center of the round sight glass.

3. Position a funnel in the opening and fill it with properly treated water.

4. Air that gets into the jacket during the filling operation must be removed,

because it will make heating less efficient. Follow the procedure in

Jacket Vacuum/Removing Air From Jacket above, to restore a negative

pressure reading.

Pressure
Gauge

Pipe
Plug

Check
Valve

Safety
Valve

Test the safety valve

at least twice monthly.