Installation and Safety Guide

5

Selecting a Site

Before you install the switch, review the following considerations about its
location.

For compatibility with Network Equipment Building System (NEBS), the
switch must be located in a network telecommunications facility.

The Rapier 48w switch requires an ambient temperature from 0ºC to 50ºC
(32ºF to 122ºF).

There should be adequate front-to-back airflow around the switch and its
vents.

The site should be dust-free and without moisture.

Humidity can be from 5% to 80% non-condensing.

You need a reliable and earthed (grounded) power supply source, preferably
dedicated and filtered.

Switch ports suitable for connection to intra-building or non-exposed
cabling are required.

Cabling must not be exposed to sources of electrical noise, such as radio
transmitters, broadband amplifiers, power lines, electric motors, and
fluorescent fixtures.

Related network devices can be connected to the switch but cannot exceed
maximum cable lengths specified in the Hardware Reference.

Ensure easy access to the switch’s power and cable connections.

You may need to remove cabinet doors to accommodate cords and cables.

When rack mounted, the switch must be located evenly to prevent uneven
mechanical loading of the rack.