3 control gas sampling based on time – cr1000, 1 terminology – Campbell Scientific SDM-CD16S 16-Channel Solid State DC Relay Controller Module User Manual
Page 20

SDM-CD16S 16 Channel Solid State DC Control Module
33: Beginning of Loop (P87)
Start fan loop
1: 0
Delay
2: 5
Loop
Count
 
34: Z=F (P30) 
PUT A "1" INTO FAN
1: 1
F
CONTROL LOCATION
2: 0
Exponent of 10
3: 20--
Z Loc :
 
35: End (P95) 
End fan loop
 
36: End (P95) 
End then do
 
37: If time is (P92) 
1: 0
minutes into a
Reset flag 2 at the
2: 15
minute
interval
end of the 15 minute
3: 22
Set low Flag 2
 
END FAN CONTROL LOGIC BASED ON TIME 
 
INPUT LOCATIONS 10 THROUGH 24 ARE NOW LOADED WITH "1" OR "0" TO SET 
PORTS ON THE SDM-CD16S. 
 
38: SDM-CD16S (P104) 
Send instructions to the
1: 1
Reps
SDM-CD16S with address 00
2: 00
Address
3: 10
Loc
 
39: End Table 1 (P) 
8.3 Control Gas Sampling Based on Time – CR1000
The SDM-CD16S is ideal for controlling low power DC operated solenoid 
valves such as might be used to control a manifold as part of a gas sampling 
system. This example shows one way to do that. 
8.3.1 Terminology
Site: A site may be the physical site where the air is sampled (i.e. intake or 
chamber) or a connection to a calibration gas. Each site has a unique 
SDMCD16S/valve setting that configures the manifold to connect gas from 
that site to the sample path of the gas analyzer. There are 8 connections to the 
“site selection” manifold. The numbers 1 through 8 identify the sites. The site 
numbers are the same as the number of the intake on the manifold and the 
number of the SDMCD16 relay controlling that valve. Sites 1 – 6 are 
connected to sample intakes to measure a atmospheric profile and sites 7 and 8 
are used for calibration gases. 
Site Sequence: The sequence in which the sites are measured is determined 
by the SiteSequence array. The sites are measured in the sequence that the site 
numbers are entered in this array, not necessarily in order of site number. 