2 controlled device connections, Address selection switch – Campbell Scientific SDM-CD16S 16-Channel Solid State DC Relay Controller Module User Manual
Page 10

SDM-CD16S 16 Channel Solid State DC Control Module
TABLE 1. Datalogger to SDM-CD16S Connections
SDM-CD16S Datalogger
Function
Logic Power
12 V on datalogger or
7 to 48 V external supply
Power
Logic Gnd
Gnd
Common ground
C1
C1 (Control Port 1)
Data
C2
C2 (Control Port 2)
Clock
C3
C3 (Control Port 3)
Enable
4.1.2 Controlled Device Connections
In most applications, the SDM-CD16S acts as a switch (controllable break) in
the positive supply of the circuit powering the controlled device. Figure 4
shows an example.
Device
SDM_CD16
Load
Power
Out
DC Power
Supply
+
GND
FIGURE 4. Typical Wiring Application
5. Address Selection Switch
Each SDM-CD16S can have 1 of 16 addresses. Shipped from the factory, the
address is set at 00. Table 2 shows switch position and the corresponding
address.