Features – Samlex America STS-30 User Manual

Page 5

background image

4 | SAMLEX AMERICA INC.

SAMLEX AMERICA INC. | 5

SecTIOn 2 |

General Information

SW1

T4

T2

r1

T6

LeD1 PCb1

T5

T3

T1

T8

T7

- r1: Transfer relay coil
- T1: Line "L", Common
- T2: Neutral "N", Common
- T3: Line "L1", No (Normally open contact of transfer relay)
- T4: Neutral "N1", No (Normally open contact of transfer relay)
- T5: Line "L2", NC (Normally closed contact of transfer relay)
- T6: Neutral "N2", NC (Normally closed contact of transfer relay)
- T7: (-) input for relay coil
- T8: (+) input for relay coil
- SW1: DIP Switch for enabling / disabling time delay for transfer

to generator

- off: enabled - delay of 20 - 25 sec. (factory preset

condition)

- oN: Disabled - no delay

- LeD1: Green LeD - on when transfer relay coil r1 is energized
- PCb1: Printed Circuit board for transfer relay control

Fig. 2 Internal layout of contacts of the transfer relay and the PCB for relay control

FeatureS

- Can be configured for transfer between Utility/Inverter or between Utility/Generator

- Multiple ¾” and 1” knockouts (7, fig. 1) have been provided on all the sides for ease

of routing the input and output cables

- Consists of heavy duty 110 VDC, Double Pole Double Throw (DPDT) relay for switching

both the Line and Neutral. (r1, fig 2)