10 | samlex america inc. samlex america inc. | 11 – Samlex America STS-30 User Manual
Page 11
10 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 11
SecTIOn 3 |
Installation
Fig. 5 Typical Generator / Power Cord
b. Start the generator. There is a pre-programmed 20 to 25 second delay in the transfer
switch. The delay is designed to allow the generator a brief warm-up period. When
the delay completes its cycle the switch should engage and the AC loads should oper-
ate normally. An audible click should sound as the relay energizes.
c. Shut down the generator. As the generator winds down the switch should disengage
without chatter or cycling. An audible click should sound as the relay de-energizes.
d. Switch oN the AC input power from the Utility/Shore Power Cord (rV). Start the gen-
erator. After the pre-programmed delay, the switch should transfer power automati-
cally from the Utility/Shore Power Cord (rV) to the generator. Listen for the audible
click as the relay is energized. Green LeD 1 will be lighted indicating that the relay has
energized. Shut down the generator and disconnect AC input power from the Utility/
Shore Power Cord (rV).
ON
LED1
TERMINALS:
T1 LINE “L”, COMMON
T2 NEUTRAL “N”, COMMON
T3 LINE “L1”, NO
(NORMALLY OPEN)
T4 NEUTRAL “N1”, NO
(NORMALLY OPEN)
T5 LINE “L2”, NC
(NORMALLY CLOSED)
T6 NEUTRAL “N2”, NC
(NORMALLY CLOSED)
T7 (–) INPUT FOR RELAY COIL
T8 (+) INPUT FOR RELAY COIL
T5
T7
T8
T1
T2
T3
20 A
FUSE
INPUT FROM SHORE POWER CORD
TO NORMALLY CLOSED (NC)
CONTACT TERMINALS T5,T6
OUTPUT TO
AC BREAKER
PANEL
INPUT FROM GENERATOR
TO NORMALLY OPEN (NO)
CONTACT TERMINALS T3,T4
30 A MAIN
BREAKER PANEL
30
MAIN
BRANCH CIRCUITS
1 2 3 4 5
T4
T6
SW1
PCB1