Samlex America SK User Manual
Page 17
3-2-3. DC Input Terminal:
Connect DC input terminal to 12V / 24V / 48V battery or the other
power sources.
【+】
represents positive, and【-】represents negative. Reverse
polarity connection will blow the internal fuse and may damage the
inverter permanently.
Model
DC Input Voltage
Minimum
Maximum
12 V
10.5
15.0
24 V
21.0
30.0
48 V
42.0
60.0
3-2-4. Use wire # 8 AWG to connect Chassis ground with vehicle chassis.
3-3. Protections Features:
Model
DC Input (VDC)
Over Temperature Protection
Over Voltage
Under
Voltage
Alarm
Under
Voltage
INTERIOR
HEAT SINK
Shut-
down
Restart
Shut-
down
Restart
Shut-
down
Restart
Shut-
down
Restart
12 V
15.3V 14.3V
11.0V
10.2V
12.7V
70℃
45℃
90℃
60℃
24 V
30.6V 28.6V
22.0V
20.3V
25.2V
48V
61.0V 57.2V
44.0V
40.8V
49.7V
WARNING!
Operating the inverter without a proper ground
Connection may cause an electrical hazard.
15
- SEC-1212 (16 pages)
- SEC-1223BBM (24 pages)
- SEC-1235 (16 pages)
- SEC-1212CE (12 pages)
- SEC-1223BBM-230 (24 pages)
- SEC-40BRM (24 pages)
- SEC-2430BRM (24 pages)
- SEC-4825BRM (36 pages)
- SEC-40BRM-220 (24 pages)
- SAM-1000-12 (32 pages)
- SAM-450-12E (16 pages)
- SAM-RC (8 pages)
- SAM-1500C-12 (32 pages)
- PST-300-12 (44 pages)
- PST-120-12 (12 pages)
- PST-600-12 (48 pages)
- PST-1500-12 (48 pages)
- RC-15A (8 pages)
- RC-200 (8 pages)
- PST-15S-12A (32 pages)
- PST-15S-12E (48 pages)
- PST-60S-12E (48 pages)
- SA-150 (15 pages)
- SA-600R (20 pages)
- SA-1000K (23 pages)
- SA-1500 (34 pages)
- SA-2000K (21 pages)
- SK (25 pages)
- SK120 (20 pages)
- S600 (24 pages)
- S1500 (39 pages)
- PSE-12125A (36 pages)
- PSE-24125A (36 pages)
- TN-1500 (20 pages)
- ST1000-112 (26 pages)
- ST1500-124 (40 pages)
- SR1000-124 (37 pages)
- BP-1210 (11 pages)
- BW-01 (2 pages)
- BATTERY MONITOR BW-03 (4 pages)
- SC-05 (12 pages)
- BBM-1225 (12 pages)
- BBM-12100 (12 pages)
- IDC-100 (4 pages)