seCtIOn 8 |

Installation

The GfCI will trip due to the following conditions:
- Leakage or ground fault
- Neutral to Ground bonding (connection) on the load side of the GfCI

!

cAUtion!

Do not feed the output from the GfCI receptacle to a Breaker Panel / Load
Center where the Neutral is bonded to the Earth Ground. This will trip the GfCI.
If the AC output is required to be fed to a Breaker Panel / Load Center, use
hardwiring connections (please see details given below).

Ac output connections for Hardwiring

for connecting the AC output of the inverter to an AC Distribution Panel / Load Center,
separate connections are available for hard wiring. Please refer to fig 6.1. Compartment
(13) contains terminals for AC output. The compartment is covered by Cover Plate (12)
with the help of 4 screws. AC output connections are as follows:

Line “L” (15) and neutral “n” (16) terminals.
Please note that Line terminal “L” (15) of the AC Terminal Block and the Line terminal
on the Line side of the GfCI are internally connected together at the PCB. Similarly,
Neutral terminal “N” (16) on the AC Terminal Block and the Neutral terminal on the
Line side of the GfCI are internally connected together at the PCB

• Hole diameter: 4 mm / 0.16"
• Set screw: #6 (UNf, 40 Threads per Inch) or M3.5 ( Coarse Pitch 0.6 mm)

Ac Ground terminal (14)

• Stud: #6 (UNC, 32 Threads Per Inch)

neutral to chassis Ground Bonding

• Neutral “N” (16) is bonded to the metal chassis of the inverter through a loop of wire

connecting the “N” terminal on the Line side of the GfCI to the chassis of the inverter.

WARninG!

RiSK oF eLectRic SHocK. When this unit is installed in vehicles and hard-wiring
connection is used to feed the AC output of the inverter to the AC Distribution
Panel / Load Center in the vehicle, it is to be ensured that Ground fault Circuit
Interrupter(s) [GfCI] are installed in the vehicle wiring system to protect all
Branch Circuits.

The following GfCIs have been tested to operate satisfactorily and are acceptable. other
types may fail to operate properly when connected to this inverter:

Mfr. of GFci

Mfr.’s Model no.

Description

Pass & Seymour

2095 Series

NEMA5-20 Duplex 20A

Leviton

7899 Series

NEMA5-20 Duplex 20A

Zhejiang Trimone

TGM20 Series

NEMA5-20 Duplex 20A