beautypg.com

Specifications – Clary S1500-601 User Manual

Page 14

background image

T H E C O N T I N U O U S P O W E R C O M P A N Y

Page 14

SPECIFICATIONS

ELECTRICAL S1500-601
Input

Voltage (Auto-selectable)

120

~

or

240

~

+10%, -20%

(without Battery discharge)

Power Factor Corrected

IAW MIL STD. 1399 Sec. 300

Frequency

50Hz / 60Hz

Current

15.6A @ 120V

~

7.8A @ 240V~

Output

Voltage

120

~

± 3%

Frequency

50Hz / 60Hz (software select)
Line Sync (software select)

Current

12.5A @ 100% non linear load

Power

1500VA, 1050W, 0.7pf

Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical

@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1

Total Harmonic Distortion (THD)

3% Typ; 5% Max.
(@100% Non-linear load)

Dynamic Response

±4% for 100% Step Load
Change,
0.5 Millisecond Recovery Time

Overload

110% for 10 Minutes;
200% for 0.5 Seconds

Efficiency (UPS)

85% Typ.

Batt Back-up (Full load\Half load)

5min\17min

UPS Protection

Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge

ENVIRONMENTAL

Operating Temperature

32

o

F to 104

o

F (0

o

C to 40

o

C)

Humidity

0% to 95% Non-condensing

Altitude

Sea Level to 10,000 Feet

Audible Noise

39-42 dBA at Five Feet

MECHANICAL

Input Inlet (6’ Line Cord Provided)

L5-20 Plug(120V~) or L6-15
Plug(240V~) to IEC320

Output (Qty.)

(1) Duplex 5-15R

Cooling

Low Velocity, Temperature
Controlled Reversible Forced
Air

Dimensions HxWxD in(cm)

14.1(36) x 6.9(17.5) x 21(53)

Weight lbs (kg)

80 (36)

DESIGN

Standard Features

Power Factor Corrected, Digital

Regenerative

™ On-Line, Sinewave

Inverter Powers Load Continuously
Extended Brownout Protection
Designed for Non-linear Loads
Continuous Operation on

-20%,+12% Line

Automatic Bypass
RS232 Data Interface
Software Selectable Output

Frequency

AC Output Switch
Auxiliary Battery Connector
Optional SNMP Interface

Specifications UL60601-1

Design

FCC Class A
IEEE 587/ANSI C62.41

MTBF

In Excess of 100,000 Hours

Typical Recharge Time to
85% Capacity at 100% Load

8 Hours

CONTROLS AND INDICATORS

Visual Indicators

Sequenced LEDs

Single LED

Battery Level, Load Level

AC Input, Inverter On, Fault
Fault Silent, AC Output,
Cold Start, Replace Battery

Front Panel Controls

Power On, Cold Start
Fault Silence, Battery Test
AC Output On/Off

Audible Alarms

Utility Interrupt, Inverter Failure
Overload, Low Battery

RS232 Data Interface (DB-9F)

Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.

Compatible with Systems
Enhancement UPS Monitor &
Control Software

Open-Collector (DB-9F)

Allows Alarm Function Monitoring

Optional SNMP Interface

(RJ45)

Allows Full Control and Monitoring
Over Network Connection.

Specifications subject to change without notice.

7/04