Control Network Components
The Avaya S8700 Media Server control network components consist of the 2 media servers, the 1 or 2 Ethernet
switch(es), and the 2 UPSs. See
‘‘Control Network Components Specifications’’
.
The internal room temperature must not exceed 43 deg C (110 deg F)
Media Gateways
The Avaya media gateways should be installed in a well-ventilated area. Maximum equipment performance is
achieved at an ambient temperature between 40 and 120 deg F (4 and 49 deg C) for a short-term operation (not
more than 72 consecutive hours or 15 days in a year) and up to 110 deg F (43 deg C) for continuous operation. The
relative humidity range is 10% to 95% at up to 84 deg F (29 deg C).
The other Environmental Considerations and System Protection requirements described in the Hardware Guide for
the Avaya™ Communication Manager under "Site Requirements" apply to the Avaya media gateways.
‘‘Media Gateway Specifications’’
below provides the dimensions for 3 types of media gateways. Refer to the
Hardware Guide for the Avaya™ Communication Manager for more detailed information.
Control Network Components Specifications
Component
Dimensions
Weight (lb/kg)
English (in.)
Metric (cm)
Us (height in rack)
Media Server
3.5h x 17d x 17w
9h x 43d x 43w
2
25/11
Ethernet Switch:
P133G2/P134G2
P333T/334T
3.5h x 14d x 19w
3.5h x 18d x 19w
9h x 35d x 48w
9h x 45d x 48w
2
2
11,13/5,6
16.5/7.5
UPS:
700 VA
1500 VA
3.5h x 19d x 17w
3.5h x 24d x 17w
9h x 48d x 43w
9h x 30d x 43w
2
2
34/15
50/23
Media Gateway Specifications
Media Gateway
Dimensions
Weight (lb/kg)
English (in.)
Metric (cm)
Us (height in rack)
MCC1
70h x 28d x 32w
178h x 71d x 81w
NA
200–800/90–363
SCC1
20h x 22d x 27w
51h x 56d x 69w
NA
125/56
G600
12h x 22d x 19w
30h x 56d x 48w
7
35–39/16–18