Gas and steam, Electric (126 kw), Electrical service specifications (per dryer) – ADC AD-170SE User Manual
Page 26
![background image](/manuals/41115/26/background.png)
22
2. Electrical Service Specifications
a. Gas and Steam Models Only
*
AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
1/23/09
** 3-Wire is available.
b. Electric Models Only
*
AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.
1/23/09
** 3-Wire is available.
GAS AND STEAM
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz
50 Hz
208
3ш
3
28.3
—
*
50
50
230
3ш
3
—
31.9
*
50
50
240
3ш
3
26.7
—
*
45
45
380
3ш
3
16.2
—
*
25
25
380
3ш
4**
—
16.1
*
25
25
400
3ш
4**
—
16.1
*
25
25
416
3ш
4**
—
16.0
*
25
25
440
3ш
3
14.4
—
*
20
20
460
3ш
3
13.9
—
*
20
20
480
3ш
3
13.9
—
*
20
20
575
3ш
3
11.4
—
*
20
20
ELECTRIC (126 kW)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz
50 Hz
416
3ш
4**
—
191
*
300
300
460
3ш
3
172
—
*
225
225