0 troubleshooting table, Operating and installation instructions preso – ARI Armaturen PRESO EN User Manual
Page 11
![background image](/manuals/409411/11/background.png)
Rev. 0040402000 0410
Page 11
Operating and installation instructions
PRESO
®
9.0 Troubleshooting table
ATTENTION !
- read point 10.0 and 11.0 prior to dismantling and repair work!
- read point 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Flange covers not removed
Remove flange covers
Little flow
Dirt sieve clogged
Clean / replace sieve
Piping system clogged
Check piping system
Pressure regulating valve
does not respond, no flow
Pressure range too high
Reset (point 6.0) or replace the
pressure regulating valve
Stainless steel bellow defective
Replace pressure regulating valve
Medium viscous or sticky
Use heating jacket
The valves and piping must be
protected against freezing and
solidifying media
Use heating jacket !
Valve installed against flow direction
Turn the valve into flow direction
Pressure regulating valve
seat leaking
Pressure regulating valve flattering
Refer to separate point “Flattering”
Medium contaminated; foreign body
between seat and disc
Replace
pressure regulating valve
Flange broken
Damage during transport
Replace
pressure regulating valve
Flange bolts not evenly tightened
Replace
pressure regulating valve
Transfer of unacceptable forces, e.g.
bending or torsional forces
Install free of tension
Pressure regulating valve
constantly open
Spring corroded by medium and broken Replace pressure regulating valve
Spindle guide corroded
Flattering
Pressure regulating valve capacity too
high
Install smaller pressure regulating
valve
Capacity too low
Pressure regulating valve not applied
unsuitable for plant conditions
Select and install suitable pressure
regulating valve