CONA

®

M - Thermostatic steam traps

8.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table
9.0 Troubleshooting table”, the supplier or manufacturer should be consulted.

9.0 Troubleshooting table

-

ATTENTION !
- It is essential that the safety regulations are observed when identifying faults.

ATTENTION !
- refer to item 10.0 and 11.0 prio
r to dismantling and repair work!
- refer to item 6.0 befo
re restarting the plant!

Fault

Possible cause

Corrective measures

No flow

Installed in wrong flow direction.

Fit valve in direction of flow arrow

Flange covers not removed

Remove flange covers

Little flow

Strainer clogged (Pos. 2)

Clean / replace strainer;
refer to item 7.1

Piping system clogged

Check piping system

Wrong controller size choosen

Correct selection acc. to flow diagram

Changed upstream pressure or back
pressure operating conditions

Correct selection acc. to flow diagram

No closure, or internal
leakage

Diaphragm capsule (Pos. 4) clogged

Clean strainer and diaphragm capsule;
refer to item 7.1

Diaphragm capsule worn out

Replace diaphragm capsule;
refer to item 7.1

Seat (Pos. 3) incorrectly screwed into
body

Check seal face between body and seat,
tighten seat correctly; refer to item 7.3

External leakage

Sealing cap (Pos. 6), top part of body
(Pos. 1

2) or cover with hex. nut (Pos. 28)

not properly tightened

Tighten; refer to item 7.3

Seal (Pos. 26) defective

Replace seal; see 7.1