8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 Troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting table
-
ATTENTION !
- It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant!
Fault
Possible cause
Corrective measures
No flow
Installed in wrong flow direction.
Fit valve in direction of flow arrow
Flange covers not removed
Remove flange covers
Little flow
Strainer clogged (Pos. 2)
Clean / replace strainer;
refer to item 7.1
Piping system clogged
Check piping system
Wrong controller size choosen
Correct selection acc. to flow diagram
Changed upstream pressure or back
pressure operating conditions
Correct selection acc. to flow diagram
No closure, or internal
leakage
Diaphragm capsule (Pos. 4) clogged
Clean strainer and diaphragm capsule;
refer to item 7.1
Diaphragm capsule worn out
Replace diaphragm capsule;
refer to item 7.1
Seat (Pos. 3) incorrectly screwed into
body
Check seal face between body and seat,
tighten seat correctly; refer to item 7.3
External leakage
Sealing cap (Pos. 6), top part of body
(Pos. 1
2) or cover with hex. nut (Pos. 28)
not properly tightened
Tighten; refer to item 7.3
Seal (Pos. 26) defective
Replace seal; see 7.1