Operating and installation instructions

3-way control valves - STEVI

®

423 (DN300)

9.0 Troubleshooting table

ATTENTION !
- read item 10.0 and 11.0 prior
to dismantling and repair work!
- read item 6.0 bef
ore restarting the plant !

Fault

Possible cause

Corrective measures

No flow

Valve closed

Open valve (using actuator)

Flange covers not removed

Remove flange covers

Little flow

Valve not sufficiently open

Open valve (using actuator)

Dirt sieve clogged

Clean / replace sieve

Piping system clogged

Check piping system

Kvs value of valve unsuitable

Fit valve with higher Kvs value

Stem moves in jerks

Stuffing box sealing too tight (for valves
with graphite packings)

Tighten packing box flange (pos. 20)
resp. nuts (pos. 22) slightly; valve must
not start leaking

Valve plug slightly seized owing to solid
dirt particles

Clean internals, smooth rough spots

Stem or plug cannot be
moved

Seatring and plug clogged with dirt

Clean seatring and plug with suitable
solvent

Valve plug seized in seatring or guide
owing to deposits or dirt in medium

Replace plug and seatring; use parts
made from different material if neces-
sary; refer to item 7.2

Stem leaking

In valves with packed stuffing boxes,
tighten screw joint (pos. 22)

Tighten packing box flange (pos. 20)
resp. nuts (pos. 22); replace packing if
necessary; refer to item 7.1.2

Leakage too high when
valve is closed

Sealing surfaces of plug eroded or worn Replace plug; refer to item 7.2
Sealing edge of seatring damages or
worn

Replace seatring; refer to item 7.2

Seatring and/or plug dirty.

Clean internal parts of the valve

Pneumatic actuator not completely
vented; spring force not fully effective

Vent actuator air chamber completely

Actuator not powerful enough

Install more powerful actuator; check
service data

Stem “hammers”

flow in the closing direction

Compare flow direction of the media
and flow marking on the valve and if
necessary rotate the valve