0 troubleshooting table – ARI Armaturen STEVI 423 DN300 EN User Manual
Page 11
![background image](/manuals/409371/11/background.png)
Rev. 0040318001 0410
Page 11
Operating and installation instructions
3-way control valves - STEVI
®
423 (DN300)
9.0 Troubleshooting table
ATTENTION !
- read item 10.0 and 11.0 prior to dismantling and repair work!
- read item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Valve closed
Open valve (using actuator)
Flange covers not removed
Remove flange covers
Little flow
Valve not sufficiently open
Open valve (using actuator)
Dirt sieve clogged
Clean / replace sieve
Piping system clogged
Check piping system
Kvs value of valve unsuitable
Fit valve with higher Kvs value
Stem moves in jerks
Stuffing box sealing too tight (for valves
with graphite packings)
Tighten packing box flange (pos. 20)
resp. nuts (pos. 22) slightly; valve must
not start leaking
Valve plug slightly seized owing to solid
dirt particles
Clean internals, smooth rough spots
Stem or plug cannot be
moved
Seatring and plug clogged with dirt
Clean seatring and plug with suitable
solvent
Valve plug seized in seatring or guide
owing to deposits or dirt in medium
Replace plug and seatring; use parts
made from different material if neces-
sary; refer to item 7.2
Stem leaking
In valves with packed stuffing boxes,
tighten screw joint (pos. 22)
Tighten packing box flange (pos. 20)
resp. nuts (pos. 22); replace packing if
necessary; refer to item 7.1.2
Leakage too high when
valve is closed
Sealing surfaces of plug eroded or worn Replace plug; refer to item 7.2
Sealing edge of seatring damages or
worn
Replace seatring; refer to item 7.2
Seatring and/or plug dirty.
Clean internal parts of the valve
Pneumatic actuator not completely
vented; spring force not fully effective
Vent actuator air chamber completely
Actuator not powerful enough
Install more powerful actuator; check
service data
Stem “hammers”
flow in the closing direction
Compare flow direction of the media
and flow marking on the valve and if
necessary rotate the valve