2 requirements at the place of installation, 3 installation instructions concerning actuators – ARI Armaturen STEVI 460 DN 15-250 EN User Manual
Page 7
Rev. 0040304000 0410
Page 7
Operating and installation instructions
Straight thr. stop valves - STEVI
®
405 / 460
(DN15-250)
5.2 Requirements at the place of installation
The place of installation should be easily accessible and provide ample space for
maintenance and removing the actuator. The valve should preferably installed vertically
with the actuator at the top. Inclined or horizontal installation without supports is permissible
only with light actuators.
For this installation position, the two distance columns (or joke) have to be above each
other in the vertical plane.
Permissible actuator weights for valves with unsupported horizontal stems:
The pipes must be lagged to protect the actuators from excessive heat. Sufficient space
must be left for the maintenance of the stem packing.
5.3 Installation instructions concerning actuators
Normally, stop valves are supplied complete with actuator fitted.
It is not permitted to mantle / dismantle actuators with valves operating and service
conditions (temperature and pressure). The actuators must be assemble as describe in the
operating instructions during conversion and maintenance.
During assembly work, the plug is not be turned on its seating at closing pressure.
When retrofitting actuators, the maximum permissible force for valve actuation must be
taken into account:
Fig. 6: Pipeline vertically
Fig. 7: Pipeline horizontally
20 kg for DN 15 - 32
40 kg for DN 125 - 150
25 kg for DN 40 - 65
55 kg for DN 125v - 150v
35 kg for DN 80-100
55 kg for DN 200 - 250
ATTENTION !
Care must be taken with the bellow type valves when actuators are mounted or
removed. (Hold the valve-stem against turning with an open-end wrench!)
Series 405
Series 460
12kN for DN 15- 50
18kN for DN 15-100
29kN for DN 65-100
37kN for DN 125v-150v
40kN for DN 125-150
37kN for DN 200-250
59kN for DN 125v-150v
59kN for DN 200-250