beautypg.com

Installation considerations, Rough in dimensions, Figure 6. table 1. rough-in-dimensions – State SBL100 199 NE User Manual

Page 8: Table 3. gas and electrical characteristics

background image

8

rough in dimensions

figure 6.

taBle 1. rough-in-dimensions

MODel DIM.

Sbl81199Ne

Sbl100199Ne

inches

cm

inches

cm

a

63 3/4

161.93

71 3/4

182.25

B

37

93.98

37

93.98

C

65

165.1

73

18542

D

52 3/4

133.99

60 3/4

154.31

E

20 3/4

52.71

20 1/2

52.07

F

21

53.34

21

53.34

G

3/4 NPT

3/4 NPT

H

53

134.62

61

154.94

I

6

15.24

6

15.24

J

27 3/4

70.49

27 3/4

70.49

K

1 1/2 NPT

1 1/2 NPT

l

1 1/2 NPT

1 1/2 NPT

Approx. Shipping Weight STD

650

295

750

341

Approx. Shipping Weight ASMe

N/a

N/a

N/a

N/a

taBle 2. reCoVery CapaCities, Based on 80% thermal effiCienCy

Model

Input

Kbtuh

Input

Kw

U.S.

Gal. liters

eff.

%

U.S. Gallons/hr and liters/hr at Temperature rise Indicated

°F

36

40

50

54

60

70

72

80

90

100

108

110

120

126

130

140

°C

20

22

28

30

33

39

40

44

50

56

60

61

67

70

72

78

Sbl81199Ne

199

81

80

GPH

531

478

382

354

319

273

265

239

212

191

177

174

159

152

147

137

45

307

lPH

2009

1808

1447

1340

1206

1033

1005

904

804

723

670

658

603

574

556

517

Sbl100199Ne

199

100

80

GPH

531

478

382

354

319

273

265

239

212

191

177

174

159

152

147

137

58

378

lPH

2009

1808

1447

1340

1206

1033

1005

904

804

723

670

658

603

574

556

517

taBle 3. gas and eleCtriCal CharaCteristiCs

model

gas type

gas supply pressure

Volts / hz

amperes

minimum

maximum

all

Natural

3.5" W.C. (0.87 kPa)

14" W.C. (3.48 kPa)

120/60

<5

installation Considerations

This manual is related to the following products: